Electrical Application Details for App #: M393395
Premises: 125 EAST 72 STREET MANHATTAN BIN: 1042844     Block: 1407   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 125 E 72 ST Census Tract:   128 Health Area:  4100
APT. 13C Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 06/26/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/15/2017 7:56 AM
Application Entered:   03/15/2017 Job Start Date:   03/16/2017
Last Change:   06/26/2018 Job End Date:   08/31/2017
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     06/15/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010687 Licensee Name: ROBERT CHIMENTI
Firm: 001905 Firm Name: ROBERT CHIMENTI
Firm Phone: 212-249-2150  Firm Address: 439 EAST 77TH STREET NEW YORK NY 10075 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $111.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MR.& MRS. ZUCKER
Owner Business Name: MR. & MRS. ZUCKER
Authorized Representative:  ROBERT CHIMENTI
Relationship To Owner:   ELECTRCIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #6/3 FEEDER
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12 CIRCUIT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  12 TO 24 CIRCUIT PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
013    11             
013  13 C                 
Buildings Total 15                
Total Units : 26 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/06/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RELOCATE EXISTING FEDERAL CIRCUIT BREAKER PANEL. RELOCATED EXISTING KITCHEN CIRCUITRY AS PER PLAN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393395
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2018 06/06/2018 AYC V (46) (4)
INSPECTION COMMENTS: FAIL
 
(2) 06/15/2018 06/18/2018 MJD C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M393395
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 013)NEUTRAL BAR IS GROUNDED BEYOND THE SERVICE SWITCH. ART. 250.24(A)(5)
RSLV 06/06/2018 06/06/2018 06/15/2018
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 013)RISER/BRANCH CIRCUIT JUNCTION BOX IS MISSING A COVER. ART. 314.28(C)
RSLV 06/06/2018 06/06/2018 06/15/2018
 
003 (252) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
(FLOOR: 013)NO SEPARATION BETWEEN LINE AND LOW VOLTAGE WIRING IN THE JUNCTIONBOX OVER THE KITCHEN ENTRYWAY. ART. 725.136
RSLV 06/06/2018 06/06/2018 06/15/2018
 
004 (999) OTHER
(FLOOR: 013)MULTI-WIRE BRANCH CIRCUIT DOES NOT HAVE SIMULTANEOUS DISCONNECTMEANS. ART. 210.4(B)
RSLV 06/06/2018 06/06/2018 06/15/2018