BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393341
Premises: 112 MULBERRY STREET MANHATTAN BIN: 1002632     Block: 205   Lot: 7
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 112 MULBERRY ST Census Tract:   41 Health Area:  6800
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   CANAL STREET,    HESTER STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/13/2017 9:33 AM
Application Entered:   03/13/2017 Job Start Date:   03/13/2017
Last Change:   08/22/2025 Job End Date:   12/29/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     05/26/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010438 Licensee Name: SILVIO HONOVIC
Firm: 000244 Firm Name: BLUE RIBBON ELEC'L CONTRS
Firm Phone: 718-625-5000  Firm Address: 500 SMITH STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $216.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (16  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GINO SORBILLO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  100 AMP THREE PHASE
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100 AMP THREE PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    12  20  12  25         
Buildings Total 12  20  12  25              
Total Units : 76 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 05/30/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393341
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/26/2017 05/30/2017 STP V (35) (6)
INSPECTION COMMENTS: FAIL.

OBJECTION FOR APPLICATION #: M393341
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 17) DEFECTIVE SWITCHES ARE IN USE
(GROUND FLOOR) AC COVER MISSING OUTSIDE 312.2
OPEN 05/26/2017 05/26/2017
 
002 (999) OTHER
(GROUND FLOOR) WORKING SPACE FOR ELECTRICAL PANEL 110.26
OPEN 05/26/2017 05/26/2017
 
003 (999) OTHER
(GROUND FLOOR) GFI NEEDED FOR FRONT BEHIND COUNTER 210.8
OPEN 05/26/2017 05/26/2017
 
004 (999) OTHER
(GROUND FLOOR) KO OPEN IN PANEL 110.12
OPEN 05/26/2017 05/26/2017
 
005 (999) OTHER
(GROUND FLOOR) ARC FLASH STICKERS FOR PANELS 110.16
OPEN 05/26/2017 05/26/2017
 
006 (999) OTHER
(GROUND FLOOR) EGC UNDERSIZED FOR AC 250.122
OPEN 05/26/2017 05/26/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back