BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393284
Premises: 340 WEST 12 STREET MANHATTAN BIN: 1077292     Block: 640   Lot: 50
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 340 W 12TH ST Census Tract:   79 Health Area:  6100
CEL,BASE,1ST,2ND,3RD,4TH Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 03/29/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/10/2017 1:19 PM
Application Entered:   03/10/2017 Job Start Date:   03/14/2017
Last Change:   03/29/2022 Job End Date:   01/31/2018
Appointment Status:   
Last Inspection By:   SAMIR BASILLI       On     03/29/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012945 Licensee Name: JAMES A SHARKEY
Firm: 003696 Firm Name: JAS ELEC'L SERVICES, INC
Firm Phone: 718-205-5618  Firm Address: 37-31 58TH STREET WOODSIDE NY 11377 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
009493 SVERDLOVE, ANDREW 003696 JAS ELEC'L SERVICES, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $935.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TODD COHEN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4#500KCMIL
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  10  8-100AMP, 4-200AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    54  27    26  54             
BAS    56  34    26  56             
001    46  23    18  46             
002    48  18    20  48             
003    37  17    18  37             
004    38  16    10  38  60         
Buildings Total 279  135    118  279     60           
Total Units : 871 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/10/2017 Notice: 1 - FIRST NOTICE 03/08/2022
Power Issued: 03/10/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393284
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/07/2022 03/08/2022 HBU V (80) (2)
INSPECTION COMMENTS: FAIL. INCOMPLETE INSPECTION. OBJECTIONS ISSUED. INSPECTED 1 SERVICE SW. 1 SE AND FC, 14 A/C MOTOR UPTO 4TH FLOOR, 6 PANELS UPTO 4TH FLOOR,6 MOTORS FOR PUMP, DEVICES AND EQUIPMENT OF CELLAR AND BASEMENT ONLY. ATOI MICHAEL.
 
(2) 03/29/2022 03/29/2022 SXB C R (75) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. SUPERCEEDED BY M00701009

OBJECTION FOR APPLICATION #: M393284
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)PAA REQUIRED, CONTRACTOR NEEDS TO ADD 15 MOTORS FOR A/C AND 6 MOTORSFOR PUMP (TOTAL 21 MOTORS AS PER CONTRACTOR COUNT).
RSLV 03/07/2022 03/07/2022 03/29/2022
 
002 (126) BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN
(CELLAR)ART. 250.52(A)(1) NOT PROVIDED WATER MAIN GROUNDING.1/0 NEEDED
RSLV 03/07/2022 03/07/2022 03/29/2022