BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393140
Premises: 101 EAST 68 STREET MANHATTAN BIN: 1081419     Block: 1403   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 695 PARK AV Census Tract:   120 Health Area:  4100
ROOF Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   HUNTER COLLEGE
DOB Cross Street(s):   EAST 68 STREET,    EAST 69 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/07/2017 5:59 PM
Application Entered:   03/07/2017 Job Start Date:   03/10/2017
Last Change:   08/22/2025 Job End Date:   05/31/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ANTOINE FLEMING       On     08/19/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011289 Licensee Name: PETER BORDUCCI
Firm: 002860 Firm Name: SOLAR ELEC. SYSTEMS, INC.
Firm Phone: 718-824-7000  Firm Address: 1402 BLONDELL AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT LEMIEUX
Owner Business Name: CITY UNIVERSITY OF NY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF                       
Buildings Total                       
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/19/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  NEW YORK STATE MESONET TOWER (WEATHER MONITORING STATION)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393140
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/19/2019 08/19/2019 AGF V (41) (4)
INSPECTION COMMENTS: FAIL ... OBJECTIONS ISSUED ; SHALL FILE FOR #2 FEEDER , OPEN KO , AND OPEN BREAKER BLANKS AT FEEDER ORIGIN , NO ACCESS TO SPLICE BOX , ALSO PANEL ON ROOF SHALL BE FILED FOR .

OBJECTION FOR APPLICATION #: M393140
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF)PAA FOR # 2 FEEDER SHALL BE FILED , ALSO ( 4 ) DEVICES ON ROOF COULDNOT BE LOCATED
OPEN 08/19/2019 08/19/2019
 
002 (999) OTHER
(ROOF) IN MACHINE RM. , GNDS ARE DBLE LUGGED IN PANEL , ART. 250
OPEN 08/19/2019 08/19/2019
 
003 (999) OTHER
(ROOF)PANEL IN MACH. RM. , OPEN KO'S AND OPEN BREAKER BLANKS , ART. 110
OPEN 08/19/2019 08/19/2019
 
004 (999) OTHER
(ROOF)VERIFICATION CAN NOT BE MADE TO SEE IF BREAKERS ARE COMPATIBLE WITHPANEL , ART. 110
OPEN 08/19/2019 08/19/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back