BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393107
Premises: 212 BROADWAY MANHATTAN BIN: 1001245     Block: 89   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 222 BROADWAY Census Tract:   15.01 Health Area:  7700
GROUND FL. Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   FULTON STREET,    ANN STREET
Status:   C - JOB IS SIGNED OFF 03/09/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/07/2017 12:41 PM
Application Entered:   03/07/2017 Job Start Date:   03/08/2017
Last Change:   03/09/2018 Job End Date:   07/31/2017
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     08/31/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012179 Licensee Name: SIMENEH SEMEA
Firm: 003892 Firm Name: E G ELECTRIC INC
Firm Phone: 212-970-7473  Firm Address: 433 BROADWAY NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $531.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122960046
Building Used As:   K - Store
Store / Other:   RESTURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: VERTS MEDITERRANEAN GRILL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  3-#10 3-#1
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  2/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    118  38    118  15     
Buildings Total 118  38    118        15      
Total Units : 295 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 08/10/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393107
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/20/2017 07/21/2017 STP V (35) (4)
INSPECTION COMMENTS: FAIL. APP NOT FILED PROPERLY, NEEDS TO ADD HEATERS MOTORS AND ALL FEEDERS. FULL INSPECT NEEDED. ONLY INSPECTED PANELS NOT WHERE THEY ARE BEING FED FROM. NEEDS TO AMMEND APP 6 SERVICE SWITCHS SHOWN, CONTRACTOR SAID ITS MISTAKE. HAVE PRINTS TO SHOW SCOPE OF WORK.
 
(2) 08/09/2017 08/10/2017 STP V X (75) (2)
INSPECTION COMMENTS: FAIL. CONTRACTOR HAD PRINTS TO SHOW SCOPE OF JOB. OBJECTIONS NOT SHOWING ON ACCELLA BUT ARE ON BIS. INSPECTION COMPLETE. DELAYED ACCESS TO SPACE.
 
(3) 08/31/2017 08/31/2017 VTC C R (47) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M393107
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) 4/0 FUSED AT 400 AMPS 240
RSLV 07/20/2017 07/20/2017 08/31/2017
 
002 (999) OTHER
(GROUND FLOOR) BOX EXTENDER NEEDED WOOD WALL 314.20
RSLV 07/20/2017 07/20/2017 08/31/2017
 
003 (999) OTHER
(GROUND FLOOR) AC DIS AND HEATER NEEDS 3FT CLEARANCE KITCHEN 110.26
RSLV 07/20/2017 07/20/2017 08/31/2017
 
004 (999) OTHER
(GROUND FLOOR) LIGHTS IN DROP CEILING NEED SUPPORT 410.36
RSLV 07/20/2017 07/20/2017 08/31/2017
 
005 (999) OTHER
(GROUND FLOOR) NIPPLE FOR PANELS OVER 60 PERCENT CHAPTER 9
RSLV 08/09/2017 08/09/2017 08/31/2017
 
006 (999) OTHER
(GROUND FLOOR) BOXS BEHIND COUNTER NEED BOND MC 250.148
RSLV 08/09/2017 08/09/2017 08/31/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order