BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393047
Premises: 28 EAST 14 STREET MANHATTAN BIN: 1009395     Block: 571   Lot: 17
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 28 E 14TH ST Census Tract:   61 Health Area:  5700
1ST Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNION SQUARE WEST
Status:   C - JOB IS SIGNED OFF 09/25/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/06/2017 3:54 PM
Application Entered:   03/06/2017 Job Start Date:   03/07/2017
Last Change:   09/25/2018 Job End Date:   02/28/2018
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     10/17/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011680 Licensee Name: STEPHEN PUCCIO
Firm: 003256 Firm Name: WEBSITE ELECTRIC CORP.
Firm Phone: 718-650-0452  Firm Address: 155 NEW DORP PLAZA STATEN ISLAND NY 10306 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $357.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   COSMETIC
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LARRY DWORKIN
Owner Business Name: DWIRKIN CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1   400 AMP SERVICE SW
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1   4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    29    20               
GND    68    25  10               
Buildings Total 97    45  17                  
Total Units : 159 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/06/2017 Notice: 1 - FIRST NOTICE 09/19/2017
Power Issued: 03/06/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INTERIOR RENOVATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393047
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/19/2017 09/19/2017 CLC V (60) (3)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 10/17/2017 10/17/2017 PHG C R (40) (0)
INSPECTION COMMENTS: PASS. OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M393047
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) SERVICE GROUND UNDER SIZE 250.66
RSLV 09/19/2017 09/19/2017 10/17/2017
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) SERVICE GROUND RACEWAY NOT CONTINUOUS 250.64 E
RSLV 09/19/2017 09/19/2017 10/17/2017
 
003 (999) OTHER
(BASEMENT) 400 AMP SERVICE SWITCHES BONDING UNDER SIZED 250.66
RSLV 09/19/2017 09/19/2017 10/17/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.