BIS Menu  |  Certs. Occupancy  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M392940
Premises: 340 EAST 116 STREET MANHATTAN BIN: 1052920     Block: 1687   Lot: 35
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 340 E 116 ST Census Tract:   188 Health Area:  2100
BASEMENT, 2ND, 3RD, 4TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   H
NEW YORK, NY 10029 Community Board:   111
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 11/16/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/03/2017 10:03 AM
Application Entered:   03/03/2017 Job Start Date:   03/03/2017
Last Change:   11/16/2017 Job End Date:   04/03/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     08/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010835 Licensee Name: HIRAM TIRADO
Firm: 002112 Firm Name: AMP ELECTRIC
Firm Phone: 718-824-4327  Firm Address: 1141 EAST 156TH STREET BRONX NY 10474 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $222.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: IRMA ORTIZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  3-ENCL,1-MAIN BKR COMBO
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  9-#6 THHN, 3-#3THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3-#3/0 CONDUCTORS
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  1 PHASE 12-1 POLE PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 0 - Removed Meters 0 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/03/2017 Notice: 1 - FIRST NOTICE 05/19/2017
Power Issued: 03/03/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADING THE ELECTRICAL SERVICE AND INSTALL NEW RISERS WITH NEW APARTMENT PANELS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M392940
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/18/2017 05/19/2017 UMS V (25) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 08/03/2017 08/03/2017 MLF C R (27) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M392940
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) NO PANEL DIRECTORY PROVIDED FOR PANELS. NEC 408
RSLV 05/18/2017 05/18/2017 08/03/2017
 
002 (999) OTHER
(FLOOR: 002)NO HANDLE TIES PROVIDED FOR MULTIWIRE BRANCH CIRCUITS. 210.4
RSLV 05/18/2017 05/18/2017 08/03/2017
 
003 (999) OTHER
(BASEMENT) NO FIRE STOPPING USED IN ALL FLOORS. NEC 300.21
RSLV 05/18/2017 05/18/2017 08/03/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.