Electrical Application Details for App #: M392722
Premises: 524 1 AVENUE MANHATTAN BIN: 1081694     Block: 962   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 530 FIRST AV Census Tract:   62 Health Area:  6000
10TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU LANGONE MEDICAL CENTER
DOB Cross Street(s):   EAST 30 STREET,    EAST 33 STREET
Status:   C - JOB IS SIGNED OFF 06/20/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/27/2017 3:47 PM
Application Entered:   02/27/2017 Job Start Date:   03/06/2017
Last Change:   06/20/2019 Job End Date:   07/07/2017
Appointment Status:   
Last Inspection By:   RIVERA, F       On     05/01/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $72.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYU LANGONE MEDICAL CENTE
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   V.P OF FACILITIES


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010    20  60    20  40         
Buildings Total 20  60    20  40              
Total Units : 141 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/24/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M392722
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/21/2017 09/22/2017 PHG J (30) (0) Y
INSPECTION COMMENTS: NO ACCESS TO SPACE. ACCESS DENIED BY HOSPITAL. FULL INSPECT NEED
 
(2) 04/24/2019 04/24/2019 AYC V (49) (4)
INSPECTION COMMENTS: FAIL. OBSERVED 10TH FLOOR: 21 LIGHTS; 31 OUTLETS; 4 SWITCHES AND BRANCH CIRCUIT WIRING.
 
(3) 05/01/2019 05/01/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008963
 
(4) 05/01/2019 05/01/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008971
 
(5) 05/01/2019 05/01/2019 FRI J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008970
 
(6) 05/01/2019 05/01/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000008968

OBJECTION FOR APPLICATION #: M392722
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010)ART. 110.3 DIRECTORY NEEDS TO BE UPDATE FOR THE WORK PERFORMED
RSLV 04/24/2019 04/24/2019 05/01/2019
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010)ART. 314.20 EXTENSION COLLARS NEEDED ON EQUIPMENT ROOM OUTLETS
RSLV 04/24/2019 04/24/2019 05/01/2019
 
003 (185) MULTIPLE SOURCE DISCONNECTS NOT GROUPED/IDENTIFIED
(FLOOR: 010)ART. 210.4(B) BRANCH CIRCUIT WIRING NEEDS TO BE GROUPED IN THEPANELS
RSLV 04/24/2019 04/24/2019 05/01/2019
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 010)ART. 422.52 GFCI PROTECTION NEEDS TO BE PROVIDED FOR THE CONFERENCEROOM WATER FOUNTAIN.
RSLV 04/24/2019 04/24/2019 05/01/2019