BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M392144
Premises: 324 EAST 79 STREET MANHATTAN BIN: 1045262     Block: 1453   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 330 E 79 ST Census Tract:   134 Health Area:  4200
APT. 3C Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 08/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/13/2017 12:30 PM
Application Entered:   02/13/2017 Job Start Date:   02/13/2017
Last Change:   08/19/2017 Job End Date:   06/13/2017
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     06/14/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010765 Licensee Name: CESAR QUERY
Firm: 002004 Firm Name: C.Q. ELECTR'L CONTRG CORP
Firm Phone: 718-204-9255  Firm Address: 723 EAST 135TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $66.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BLADIMIR BRICENO
Authorized Representative:  TOMAS MONTALVO
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100 AMP 1 PHASE 16 CIRC.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3C  10  25    10             
Buildings Total 10  25    10                
Total Units : 54 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/23/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  DOB-2K17-008 PARTIAL RENOVATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M392144
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/19/2017 05/23/2017 FDY V (45) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED. INSPECTION COMPLETED.
 
(2) 06/14/2017 06/14/2017 GYM C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M392144
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 003) 240.4(D) OVERCURRENT PROTECTION OVERSIZED.
RSLV 05/19/2017 05/19/2017 06/14/2017
 
002 (999) OTHER
(FLOOR: 003)250.102(B) BONDING JUMPER MISSING FROM BOX IN KITCHEN CEILING TOOUTLET BOXES IN KITCHEN. CHANGED OVER FROM CONDUIT TO GREENFIELD.
RSLV 05/19/2017 05/19/2017 06/14/2017
 
003 (999) OTHER
(FLOOR: 003) 310.15(B)(2)(A) WIRES UNDERSIZED.
RSLV 05/19/2017 05/19/2017 06/14/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order