Electrical Application Details for App #: M392023
Premises: 550 WEST 33 STREET MANHATTAN BIN: 1091590     Block: 702   Lot: 150
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 560 W 33 ST Census Tract:   99 Health Area:  5500
FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Related Job Number:    121192618
DOB Cross Street(s):   HUDSON BOULEVARD EAST,    11 AVENUE
Status:   C - JOB IS SIGNED OFF 04/30/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/08/2017 5:07 PM
Application Entered:   02/08/2017 Job Start Date:   02/08/2017
Last Change:   04/30/2024 Job End Date:   01/02/2018
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     04/25/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012629 Licensee Name: ROBERT M MARKS
Firm: 004464 Firm Name: DIFAZIO ELECTRIC NY, INC
Firm Phone: 212-684-5350  Firm Address: 32 EAST 31ST STREET, 8TH FLR NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (324  Stores, 354 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RONALD WACKROW
Owner Business Name: RELATED COMPANIES
Authorized Representative:   WACKROW
Relationship To Owner:   EXEC VP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/19/2024
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ONE (1) ELEVATOR (SE1): NOT RESPONSIBLE FOR MAIN LINE DISCONNECT SW, CAB LIGHTING DISCONNECT SW, FEEDERS & BRANCH CIRCUITS TO CONTROLLERS, PIT & MACHINE ROOM LIGHTING, OVERHEAD LIGHTING & SUMP PUMP WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M392023
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/13/2024 03/14/2024 HBU N (25) (0) Y
INSPECTION COMMENTS: NO ACCESS. INCOMPLETE INSPECTION. CALLED CONTRACTOR AND HE SAID THAT INSPECTION CANCELED. OK TO PROCEED AS PER DIRECTED BY OFFICE GIG.
 
(2) 03/18/2024 03/19/2024 FPY V (45) (4)
INSPECTION COMMENTS: INSPECTION INCOMPLETE. CONTRACTOR WAS NOT FAMILIAR WITH WORK, COULD NOT VERIFY BONDING TO BUILDING STEEL. ATOI CHRIS/PHIL
 
(3) 04/25/2024 04/25/2024 ASK C R (39) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. ATOI CHRIS

OBJECTION FOR APPLICATION #: M392023
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ALL FLOORS)110.2A DEFECTIVE GFCI RECEPTACLE IS IN USE IN MACHINE ROOM
RSLV 03/18/2024 03/18/2024 04/25/2024
 
002 (227) TRANSFORMER GROUNDING CONDUCTOR RACEWAY IS NOT CONTINUOUS
(ALL FLOORS)250.68 GROUNDING WAS NOT CONNECTED IN JUNCTION BOX FOR TRANSFORMERAND DISCONNECTS
RSLV 03/18/2024 03/18/2024 04/25/2024
 
003 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(ALL FLOORS) 250.97 INSUFFICIENT BONDING FOR CONCENTRIC KOS
RSLV 03/18/2024 03/18/2024 04/25/2024
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS)300.4 NO BUSHING PROVIDED GOT CONDUCTORS IN DISCONECTS AND JUNCTIONBOX
RSLV 03/18/2024 03/18/2024 04/25/2024