| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
1X200A |
| C. 201 Up to 600 AMPS |
1 |
1X400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 X 3/O |
| D. Over 250 MCM |
1 |
1X 500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1X 200A MAIN BREAKER 42SK |
| D. 3 Phase Over 225 AMPS |
1 |
1X 400A MAIN BREAKER 42SK |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(313) |
SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET (FLOOR: 009)NO SIGNS FOR ELECTRICAL CLOSETS AND WAS BEING USED FOR STORAGE.110.26 |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 002 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 009) UNUSED HOLES IN PANEL AND BOX FOR FURNITURE |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 003 |
(999) |
OTHER (FLOOR: 009)NEC 110.16 NO ARC FLASH WARNING LABELS ON ANY OF 3 PANELS |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 004 |
(999) |
OTHER (FLOOR: 009)NEC 210.4(D) NO SIMULTANEOUS TRIP BREAKER USED ON 2 POLE CIRCUITS |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 005 |
(999) |
OTHER (FLOOR: 009)NEC 314.20 BOXES SET BACK EXCEEDING ALLOWABLE LIMITS IN KITCHEN |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 006 |
(999) |
OTHER (FLOOR: 009)NEC110.12 (B) SEALTITE CHANGE OVER TO PIPE HAS NO FITTINGS USEDWHATSOEVER. |
OPEN |
01/03/2019 |
01/03/2019 |
|
| |
| 007 |
(999) |
OTHER (FLOOR: 009)NEC 250.8 DISCONNECTS FOR AC UNITS DOUBLE LUGGED AND NOT PROPERLYGROUNDED |
OPEN |
01/03/2019 |
01/03/2019 |
|