BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M391901
Premises: 207 WEST 25 STREET MANHATTAN BIN: 1014211     Block: 775   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 207 W 25 ST Census Tract:   91 Health Area:  5200
9 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/06/2017 8:14 PM
Application Entered:   02/06/2017 Job Start Date:   02/07/2017
Last Change:   08/22/2025 Job End Date:   02/05/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PAUL MATASKA       On     01/03/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011749 Licensee Name: JEROME DALY
Firm: 003344 Firm Name: AMRA ELECTRICAL CORP
Firm Phone: 718-444-5209  Firm Address: 1415 UTICA AVENUE BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $618.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EYAL MORAD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1X200A
C. 201 Up to 600 AMPS  1  1X400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 X 3/O
D. Over 250 MCM  1  1X 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1X 200A MAIN BREAKER 42SK
D. 3 Phase Over 225 AMPS  1  1X 400A MAIN BREAKER 42SK
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009  OFF9  236  167    62  236  67  36     
Buildings Total 236  167    62  236     67     36      
Total Units : 804 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 02/06/2017 Notice: 1 - FIRST NOTICE 01/03/2019
Power Issued: 02/06/2017 Response:  

Follow-Up:
Contractor's Comments:  SERVICE WORK GENERAL WIRING , HVAC .

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M391901
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2018 08/15/2018 CBK N (50) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(2) 12/18/2018 12/18/2018 DWB N (35) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR, NO SHOW.
 
(3) 01/03/2019 01/03/2019 PMK V (150) (7)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M391901
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (313) SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET
(FLOOR: 009)NO SIGNS FOR ELECTRICAL CLOSETS AND WAS BEING USED FOR STORAGE.110.26
OPEN 01/03/2019 01/03/2019
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 009) UNUSED HOLES IN PANEL AND BOX FOR FURNITURE
OPEN 01/03/2019 01/03/2019
 
003 (999) OTHER
(FLOOR: 009)NEC 110.16 NO ARC FLASH WARNING LABELS ON ANY OF 3 PANELS
OPEN 01/03/2019 01/03/2019
 
004 (999) OTHER
(FLOOR: 009)NEC 210.4(D) NO SIMULTANEOUS TRIP BREAKER USED ON 2 POLE CIRCUITS
OPEN 01/03/2019 01/03/2019
 
005 (999) OTHER
(FLOOR: 009)NEC 314.20 BOXES SET BACK EXCEEDING ALLOWABLE LIMITS IN KITCHEN
OPEN 01/03/2019 01/03/2019
 
006 (999) OTHER
(FLOOR: 009)NEC110.12 (B) SEALTITE CHANGE OVER TO PIPE HAS NO FITTINGS USEDWHATSOEVER.
OPEN 01/03/2019 01/03/2019
 
007 (999) OTHER
(FLOOR: 009)NEC 250.8 DISCONNECTS FOR AC UNITS DOUBLE LUGGED AND NOT PROPERLYGROUNDED
OPEN 01/03/2019 01/03/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back