Electrical Application Details for App #: M391839
Premises: 423 HUDSON STREET MANHATTAN BIN: 1010402     Block: 602   Lot: 68
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 435 HUDSON ST Census Tract:   69
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
Special Place Name:   HINES/38519
DOB Cross Street(s):   LEROY STREET,    MORTON STREET
Status:   C - JOB IS SIGNED OFF 07/25/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/06/2017 Job Start Date:   01/30/2017
Last Change:   07/25/2017 Job End Date:   04/01/2017
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     07/23/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011809 Licensee Name: ARTHUR A GROSSMAN
Firm: 000176 Firm Name: ATLAS-ACON ELEC. SERVICE
Firm Phone: 212-741-0600  Firm Address: 283 HUDSON STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,502.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54200     Submittal #: 16A0846  
Owner / Occup: FRANK SAPHIRE
Owner Business Name: HINES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1-3000
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  1-4#1
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  13  500MCM.2-4#350 3-4#600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1-3 PHASE 100 AMP 42 CKT
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15    15             
Buildings Total 15    15                
Total Units : 38 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 9 + New Meters 1 - Removed Meters 8 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/06/2017 Notice: 1 - FIRST NOTICE 04/26/2017
Power Issued: 02/06/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVAL OF SWBD #2 & REPLACE WITH NEW SWITCHGEAR CON EDSHUTDOWN REQUIRED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M391839
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/25/2017 04/26/2017 PHG V (85) (5)
INSPECTION COMMENTS: CONTRACTOR TO UPDATE APP FOR ALL WORK DONE
 
(2) 07/23/2017 07/24/2017 TUR C R (80) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M391839
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(BASEMENT) TAPS FOR METERS OVER 25 FT 240.21
RSLV 04/25/2017 04/25/2017 07/23/2017
 
002 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(BASEMENT) TAP WIRE DOES NOT MEET FUSE SIZE FRO ALL METERS 240.21
RSLV 04/25/2017 04/25/2017 07/23/2017
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) COPPER CLAD 500 NOT RATED FOR 400 AMPS 310.15
RSLV 04/25/2017 04/25/2017 07/23/2017
 
004 (999) OTHER
(BASEMENT) NEUTRAL AND GROUND NOT BONDED IN FA SERVICE SW 250.24
RSLV 04/25/2017 04/25/2017 07/23/2017
 
005 (999) OTHER
(BASEMENT) HANDLE TIES NOT PROVIDED FOR MULTI WIRE CKT 210.4
RSLV 04/25/2017 04/25/2017 07/23/2017