| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(290) |
BATHROOM BRANCH CIRCUIT NOT PROVIDED (FLOOR: 002) 210.11 (C)(3) NOT PROVIDED BRANCH CTO TO BATHROOM . |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 002 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 002) 110.12 (A) MISSING KO'S AT ELECTRICAL PANEL |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 002) 408.4 NOT PANEL DIRECTORY. |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 002) 210.12 (B) NOT AFCI PROTECTION PROVIDED |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 002) 314.72 D MICROWAVE OUTLET NOT ACCESIBLE |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 002) 314.20 BOXES SET BACK WITH NON COMBUSTIBLE 1/4" T-OUT |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 007 |
(999) |
OTHER (FLOOR: 002) 210.4 (B) NOT SIMULTANEOUS DISCONNECT AT 2 POLE CB |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |
| |
| 008 |
(999) |
OTHER (FLOOR: 002) 330.108 MC CABLE NOT GROUNDED AT ELECTRICAL PANEL. |
RSLV |
10/01/2018 |
10/01/2018 |
10/17/2018 |