Premises: 560 1 AVENUE MANHATTAN BIN: 1085695     Block: 962   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 560 FIRST AV Census Tract:   62 Health Area:  6000
11TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU LANGONE MEDICAL CENTER
DOB Cross Street(s):   EAST 30 STREET,    EAST 33 STREET
Status:   C - JOB IS SIGNED OFF 08/21/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/26/2017 1:55 PM
Application Entered:   01/26/2017 Job Start Date:   02/06/2017
Last Change:   08/21/2019 Job End Date:   10/20/2017
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     08/20/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $86.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYULANGONE MEDICAL CENTER
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   VP OF FACILITIES


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011    42  44    38  72             
Buildings Total 42  44    38  72                
Total Units : 196 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/24/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M391424
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/21/2017 09/22/2017 PHG V (45) (2)
INSPECTION COMMENTS: INSPECTED ONLY PANEL AND STAFF LOUNGE. NO ACCESS TO PATIENT ROOMS AND EM PANEL PULL BOX ECT. FULL INSPECT NEEDED
 
(2) 07/17/2019 07/24/2019 AYC V R (94) (2)
INSPECTION COMMENTS: FAIL, SEE OBJECTIONS.
 
(3) 07/26/2019 07/26/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000015991
 
(4) 08/20/2019 08/20/2019 TUR C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000018366

OBJECTION FOR APPLICATION #: M391424
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
(FLOOR: 011) 17 #10 WIRES IN 1 INCH PIPE
RSLV 09/21/2017 09/21/2017 07/17/2019
 
002 (999) OTHER
(FLOOR: 011) NO ACCESSES TO LIGTING BOX IN STAFF LOUNGE 314.29
RSLV 09/21/2017 09/21/2017 07/17/2019
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)ART. 314.20 EXTENSION COLLARS NEEDED AT THE WALLPAPERED SURFACES.
RSLV 07/17/2019 07/17/2019 07/26/2019
 
004 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(FLOOR: 011)ART. 210.4(D) BRANCH CIRCUITS ARE NOT GROUPED IN PANEL E11-4A
RSLV 07/17/2019 07/17/2019 08/20/2019