BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M390809
Premises: 448 EAST 58 STREET MANHATTAN BIN: 1040544     Block: 1369   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 SUTTON PL Census Tract:   106.01 Health Area:  4900
SUTTON PLACE/11/B Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):       
Status:   C - JOB IS SIGNED OFF 11/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/10/2017 2:20 PM
Application Entered:   01/10/2017 Job Start Date:   01/10/2017
Last Change:   11/04/2017 Job End Date:   01/10/2018
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     10/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012361 Licensee Name: ANGELO DOMINGUEZ
Firm: 004263 Firm Name: ALLTECH ELECL CONTNG CORP
Firm Phone: 646-491-2088  Firm Address: 227 SEA BREEZE AVE., STE 201 BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $71.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CAROL KLEIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011    18  25  11  18             
Buildings Total 18  25  11  18                
Total Units : 74 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 08/21/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS JOB IS A PARTIAL RENOVATION, NOT ALL CIRCUITS ARE BEING REPLACED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M390809
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/19/2017 07/19/2017 HRB V (70) (4)
INSPECTION COMMENTS: CONTRACTOR MUST AMEND HIS APP TO SHOW ALL WORK THAT WAS DONE
 
(2) 08/11/2017 08/11/2017 GYM H X (65) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(3) 08/21/2017 08/21/2017 MLF J X (39) (0) Y
INSPECTION COMMENTS: CONTRACTOR NEEDS TO AMMEND/WITHDRAW APP TO REFLECT ACTUAL ADRESS
 
(4) 10/10/2017 10/10/2017 TUR N (10) (0) Y
INSPECTION COMMENTS: NO ACCESS TO M401171 AND OBJECTIONS THIS APPLICATION
 
(5) 10/25/2017 10/26/2017 MLF C R (25) (0)
INSPECTION COMMENTS: REPLACED BY M401171

OBJECTION FOR APPLICATION #: M390809
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (185) MULTIPLE SOURCE DISCONNECTS NOT GROUPED/IDENTIFIED
(FLOOR: 011) 12/3 AND 12/2 CIRCUITS ARE NOT GROUPED IN THE PANEL
RSLV 07/19/2017 07/19/2017 10/25/2017
 
002 (229) SPLICE BOXES NOT ACCESSIBLE
(FLOOR: 011) FEEDING PANEL
RSLV 07/19/2017 07/19/2017 10/25/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 011) FOR AC OUTLETS
RSLV 07/19/2017 07/19/2017 10/25/2017
 
004 (999) OTHER
(FLOOR: 011)MISSING SPARK GUARDS ARE MISSING FOR ALL TILE WALLS (406.4)
RSLV 07/19/2017 07/19/2017 10/25/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order