| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
11/25/2019 |
11/25/2019 |
AGF |
N |
|
|
(29) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
NO SHOW ... CONTRACTOR IS NOT PRESENT , INSPECTOR MADE CONTACT VIA TELEPHONE AND WAS INFORMED THAT AN INDIVIDUAL SHOULD BE ON SITE , INSPECTOR WAITED IN LOBBY OF HOSPITAL AND NO ONE SHOWED UP .
|
| |
| (2) |
12/10/2019 |
12/10/2019 |
SWR |
V |
|
|
(30) |
|
(3) |
|
| INSPECTION COMMENTS:
|
FAIL. OBJECTION ISSUED.
|
| |
| (3) |
02/18/2020 |
02/18/2020 |
PHG |
V |
X |
|
(30) |
|
(2) |
|
| INSPECTION COMMENTS:
|
CONTRACTOR TO PROVIDED LISTING FOR MOTOR SPLICE MADE OB BOTTOM OF ELEVATOR
|
| |
| (4) |
03/23/2020 |
03/23/2020 |
PHG |
V |
X |
|
(45) |
|
(1) |
|
| INSPECTION COMMENTS:
|
OBJECTIONS THAT WHERE REMOVED ON ACELLA SHOW BACK UP ON ACELLA SYSTEM NEW OBJECTION ON BIZ DOESN'T NOT SHOW ON ACELLA OBJECTION NO FIXED
|
| |
| (5) |
05/04/2020 |
05/05/2020 |
STP |
V |
Y |
|
(60) |
|
(3) |
|
| INSPECTION COMMENTS:
|
FAIL. HAVE REPRESENTATIVE WHO KNOWS JOB. REVIEW JOB AND OBJECTIONS BEFORE SUBMITTING NEW REQUEST.
|
| |
| (6) |
08/20/2020 |
08/21/2020 |
CBK |
N |
|
|
(5) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
DID NOT REACH IN TIME, STOP WAS TOO FAR.
|
| |
| (7) |
10/08/2020 |
10/09/2020 |
STP |
V |
Y |
|
(30) |
|
(1) |
|
| INSPECTION COMMENTS:
|
FAIL. CONTRACTOR SHOWED UP 10 MINUTES LATE. NEED TO SEE LOAD SIDE MC TO LIFT WIRING. INSPECTION INCOMPLETE.
|
| |
| (8) |
01/13/2021 |
01/13/2021 |
STP |
C |
R |
|
(60) |
|
(0) |
|
| INSPECTION COMMENTS:
|
PASS. OBJECTIONS REMOVED. INSPECTION COMPLETE.
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (GROUND FLOOR)ELEVATOR/ LIFT NYC ID # IW7179 DISCONNECT OVER FUSED ART 620.61 |
RSLV |
12/10/2019 |
12/10/2019 |
05/04/2020 |
| |
| 002 |
(999) |
OTHER (GROUND FLOOR) MECHANICAL CONTINUITY. ART 300.12 |
RSLV |
12/10/2019 |
12/10/2019 |
01/13/2021 |
| |
| 003 |
(999) |
OTHER (GROUND FLOOR) ARC FLASH WARNING STICKER NOT PROVIDED. ART 110.16 |
RSLV |
12/10/2019 |
12/10/2019 |
05/04/2020 |
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 001)CONTRACTOR TO PROVIDED LISTING OF MOTORS FOR HANDY LIFT |
RSLV |
02/18/2020 |
02/18/2020 |
01/13/2021 |
| |
| 005 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (FLOOR: 001) SPLICE POINT DOES NOT CONFORM TO 400.14 |
RSLV |
02/18/2020 |
02/18/2020 |
10/08/2020 |
| |
| 006 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (GROUND FLOOR) SPLICE POINT DOES NOT CONFORM TO 400.14 |
RSLV |
03/23/2020 |
03/23/2020 |
10/08/2020 |
| |
| 007 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (GROUND FLOOR)620.21 C FLEXIBLE CORD FOR LIFT NOT PERMITTED OVER 30 VOLTS/OVER 6' |
RSLV |
05/04/2020 |
05/04/2020 |
01/13/2021 |
| |
| 008 |
(162) |
CORD CONNECTORS NOT PROPERLY UTILIZED/LISTED (GROUND FLOOR)110.3 400.1 FMC CONNECTOR USED AT 4" BOX FOR FLEXIBLE CORD |
RSLV |
05/04/2020 |
05/04/2020 |
10/08/2020 |
| |
| 009 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (GROUND FLOOR)110.3 SUBMIT PROPER US LISTING/APPROVAL FOR MOTOR IN USE |
RSLV |
05/04/2020 |
05/04/2020 |
01/13/2021 |
| |
| 010 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (GROUND FLOOR)314.29 LOAD SIDE DISCONNECT MC AND 4" UNDER LIFT FLEXIBLE CORD |
RSLV |
10/08/2020 |
10/08/2020 |
01/13/2021 |