BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M390609
Premises: 148 BROADWAY MANHATTAN BIN: 1001087     Block: 64   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 150 BROADWAY Census Tract:   15.02 Health Area:  7700
CELLAR, 19TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   ZOLA
DOB Cross Street(s):   LIBERTY STREET,    CORTLANDT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/04/2017 9:32 AM
Application Entered:   01/04/2017 Job Start Date:   01/05/2017
Last Change:   08/22/2025 Job End Date:   04/30/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     09/13/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010878 Licensee Name: FRANK PUGLIESE
Firm: 003455 Firm Name: PATRIOT ELECTRIC CORP
Firm Phone: 718-736-8733  Firm Address: 15-17 126TH STREET 3RD FLOOR COLLEGE POINT NY 11356 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011850 ST. JOHN, JAMES P 003455 PATRIOT ELECTRIC CORP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $397.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ERIN MCGUINESS
Owner Business Name: ALL BUILDING CONSTRUCTION
Authorized Representative:  ERIN MCGUINESS
Relationship To Owner:   OWNER'S REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  #4, #2 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100 AMP
D. 3 Phase Over 225 AMPS  1  400 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
019    71  65    15  24  18     
Buildings Total 71  65    15  24     18         
Total Units : 198 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/13/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  LIGHTING, RECEPTACLES, PANEL RISER FROM BASEMENT, HVAC

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M390609
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/13/2017 09/13/2017 VTC V (66) (5)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M390609
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 019) CABLE EXPOSED IN ELECTRIC CLOSET
OPEN 09/13/2017 09/13/2017
 
002 (313) SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET
(FLOOR: 019) SIGNAGE NOT PROVIDED FOR ELECTRIC CLOSET
OPEN 09/13/2017 09/13/2017
 
003 (999) OTHER
(FLOOR: 019)EXTENSION COLLAR NOT PROVIDED FOR MICROWAVE OUTLET 314.20
OPEN 09/13/2017 09/13/2017
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
(CELLAR) LARGE COVER MISSING
OPEN 09/13/2017 09/13/2017
 
005 (999) OTHER
(CELLAR) FIRESTOP NOT PROVIDED IN CELLAR, AND 19TH FLOOR 300.21
OPEN 09/13/2017 09/13/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back