NYC Department of Buildings
Electrical Application Details for App #: M390553
Premises: 329 EAST 6 STREET MANHATTAN BIN: 1006296     Block: 448   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 329 E 6ST Census Tract:   38 Health Area:  6500
CEL, 1-5 FL Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 07/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/30/2016 11:28 AM
Application Entered:   12/30/2016 Job Start Date:   01/03/2017
Last Change:   07/20/2018 Job End Date:   06/03/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     07/20/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011720 Licensee Name: ERIC K AU
Firm: 003306 Firm Name: ERIC & NG ELEC'L, INC.
Firm Phone: 212-673-4118  Firm Address: 155 SUFFOLK STREET NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $140.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PARVINDER SINGH
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  20 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      20  10  10             
002      10             
005      20  10  10             
Buildings Total   50  10  25  25                
Total Units : 110 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/22/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M390553
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/15/2018 02/16/2018 HRB N (35) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 03/22/2018 03/22/2018 PHG V (50) (9)
INSPECTION COMMENTS: CONTRACTOR TO FIX APP TO REFLECT WORK FULL INSPECT NEEDED WHEN CONTRACTOR FIXES APP AND ADDS DIRECTORY INSPECTED APT 2 7 AND 8 ONLY FULL INSPECT NEEDED
 
(3) 05/16/2018 05/16/2018 STP J Y (45) (0)
INSPECTION COMMENTS: JOB IN PROGRESS. SPECIFY APARTMENTS WORKED IN ON NEW APP M00041641. DUE TO ACCESS UNABLE TO CHECK LAUNDRY CIRCUITS.
 
(4) 07/20/2018 07/20/2018 MLF C R (35) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: M390553
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
(FLOOR: 001) ONLY ONE CKT IN KITCHEN COUNTER 210.52
RSLV 03/22/2018 03/22/2018 05/16/2018
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(ALL FLOORS) OUTLETS NOT GROUNDED T OUT 250.146
RSLV 03/22/2018 03/22/2018 05/16/2018
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) NO CHANGE OVER FOR ALL 1/2 PIPE WITH 1900 BOXES 250.8
RSLV 03/22/2018 03/22/2018 05/16/2018
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) ALL MC CABLE NOT BONDED TO BOX 250.148
RSLV 03/22/2018 03/22/2018 05/16/2018
 
005 (340) RECEPTACLES NOT TAMPERPROOF
(ALL FLOORS) KITCHEN COUNTER 406.11
RSLV 03/22/2018 03/22/2018 05/16/2018
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) NO DIRECTORY ALL APTS
RSLV 03/22/2018 03/22/2018 05/16/2018
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) NO GFCI PROTECTION ON KITCHEN COUNTER 210.8
RSLV 03/22/2018 03/22/2018 05/16/2018
 
008 (999) OTHER
(ALL FLOORS) SHEET ROCK SCREWS FOR OUTLETS 110.3
RSLV 03/22/2018 03/22/2018 05/16/2018
 
009 (999) OTHER
(ALL FLOORS) NO 120V LAUNDRY CKT PROVIDED FOR LAUNDRY AREA 210.11
RSLV 03/22/2018 03/22/2018 07/20/2018