Electrical Application Details for App #: M390501
Premises: 126 ORCHARD STREET MANHATTAN BIN: 1005304     Block: 410   Lot: 4
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 130 ORCHARD ST Census Tract:   18 Health Area:  7400
BASEMENT / GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 08/29/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/29/2016 9:43 AM
Application Entered:   12/29/2016 Job Start Date:   12/29/2016
Last Change:   08/29/2017 Job End Date:   12/26/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     07/31/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012704 Licensee Name: PIOTR MISA
Firm: 004541 Firm Name: P & Z ELECTRIC CORP
Firm Phone: 718-360-0858  Firm Address: 3606 37TH STREET ASTORIA NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $567.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   GALERY/ RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NEW YORK GALLERYLLC
Authorized Representative:  WILLIAM GIOIELLI
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  8X 500MCM
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  4X 4/0
D. 3 Phase Over 225 AMPS  1  8X 500MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BAS  31  21  31  19  10     
GND  GND  89  25      89             
Buildings Total 120  46  120     19     10      
Total Units : 321 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 25 + New Meters 1 - Removed Meters 15 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/29/2016 Notice: 1 - FIRST NOTICE 07/20/2017
Power Issued: 12/29/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M390501
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/19/2017 07/20/2017 CBK V (123) (6)
INSPECTION COMMENTS: SEE OBJECTION DETAILS. DID NOT INSPECT AC ON ROOF, AND I DID NOT SEE RECEPTACLES SPLICES/GROUNDING, CONTR. DID NOT HAVE TOOL.
 
(2) 07/31/2017 08/01/2017 TOR C R (40) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M390501
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(ALL FLOORS) TEMPS NOT REMOVED FROM CEILING.
RSLV 07/19/2017 07/19/2017 07/31/2017
 
002 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) WATER METER NOT JUMP. 250.53
RSLV 07/19/2017 07/19/2017 07/31/2017
 
003 (313) SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET
(BASEMENT) NO SIGNAGE ON ELECTRIC CLOSET.
RSLV 07/19/2017 07/19/2017 07/31/2017
 
004 (999) OTHER
(BASEMENT) AC UNIT OVER-FUSED. 110.3
RSLV 07/19/2017 07/19/2017 07/31/2017
 
005 (999) OTHER
(BASEMENT) NO ARC-FLASH WARNING ON EQUIPMENTS. 110.16
RSLV 07/19/2017 07/19/2017 07/31/2017
 
006 (999) OTHER
(GROUND FLOOR) NO DISCONNECT ON FRONT GATE MOTORS. 430.101
RSLV 07/19/2017 07/19/2017 07/31/2017