BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M390437
Premises: 212 BROADWAY MANHATTAN BIN: 1001245     Block: 89   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 222 BROADWAY Census Tract:   15.01 Health Area:  7700
2FL Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   FULTON STREET,    ANN STREET
Status:   C - JOB IS SIGNED OFF 05/12/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/27/2016 3:02 PM
Application Entered:   12/27/2016 Job Start Date:   12/27/2016
Last Change:   05/12/2017 Job End Date:   06/01/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/11/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011332 Licensee Name: SPIRO SINANIS
Firm: 003482 Firm Name: METROPOLIS ELECTRIC CORP
Firm Phone: 718-205-7605  Firm Address: 110 WEST 40 STREET SUITE 600 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $211.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: L&L HOLDING COMPANY, LLC
Authorized Representative:  DAVID BERK
Relationship To Owner:   PROPERTY MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  SETS 4/0AWG
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002                  150 
Buildings Total                    150 
Total Units : 154 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/24/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REUSED FUSED SWITCH IN EXISTING RETAIL MDP FOR SERVICE TO RETAIL "C" SPACE. TERMINATE IN PULLBOX FOR PICKUP BY OTHERS UNDER RETAIL FITOUT PROGRAM.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M390437
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/23/2017 01/24/2017 CBK V (45) (3)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 04/07/2017 04/07/2017 CBK J Y (40) (0)
INSPECTION COMMENTS: OBJECTION PARTIALLY REMOVED.
 
(3) 05/11/2017 05/12/2017 TOR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M390437
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (131) BONDING JUMPER TO BUILDING STEEL IS NOT OF PROPER SIZE
(BASEMENT) GEC FOR 150 KVA IS UNDERSIZE.
RSLV 01/23/2017 01/23/2017 04/07/2017
 
002 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(BASEMENT) GEC IS NOT CONTINUOUS TO X OF O.
RSLV 01/23/2017 01/23/2017 05/11/2017
 
003 ( 55) CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL
(BASEMENT) # 2 GROUNDING FOR TRANSFORMER RUN IN PARALLEL.
RSLV 01/23/2017 01/23/2017 05/11/2017