| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(143) |
LUMINAIRES NOT PROPERLY SUPPORTED/SECURED (FLOOR: 008) LAYIN LIGHT FIXTURES NOT SUPPORTED. ART. 410.36(B) |
RSLV |
04/06/2018 |
04/06/2018 |
07/18/2018 |
| |
| 002 |
(999) |
OTHER (FLOOR: 008)GAP BETWEEN WALLPAPERED FINISH SURFACE AND RECEPTACLES. ART. 312.3 |
RSLV |
04/06/2018 |
04/06/2018 |
07/18/2018 |
| |
| 003 |
(999) |
OTHER (FLOOR: 008) BRANCH CIRCUITS NOT GROUPED IN THE PANEL. ART. |
RSLV |
04/06/2018 |
04/06/2018 |
07/18/2018 |
| |
| 004 |
(999) |
OTHER (FLOOR: 018)DISCONNECT SWITCHES NOT MARKED FOR HIGH VOLTAGE AND ARC FLASH. ARTS.110.3 & 110.16 |
RSLV |
04/06/2018 |
04/06/2018 |
07/18/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 018)BUSHINGS MISSING IN HIGH VOLTAGE DISCONNECT SWITCH. ART. 300.4(G |
RSLV |
04/06/2018 |
04/06/2018 |
07/18/2018 |
| |
| 006 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (FLOOR: 008)SJ CORD USED A PERMANENT WIRING METHOD IN THE WALL FOR CABINETLIGHTS. ART. 400.8 |
RSLV |
07/18/2018 |
07/18/2018 |
08/03/2018 |
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008) OPEN KO. ART. 110.12(A) |
RSLV |
07/18/2018 |
07/18/2018 |
08/03/2018 |
| |
| 008 |
(216) |
LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE (FLOOR: 008)NO SEPARATION BETWEEN LINE AND LOW VOLTAGE WIRING IN CEILINGJUNCTION BOX. ART. 725.138 |
RSLV |
07/18/2018 |
07/18/2018 |
08/03/2018 |