Premises: 560 1 AVENUE MANHATTAN BIN: 1085695     Block: 962   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 562 FIRST AV Census Tract:   62 Health Area:  6000
8TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU LANGONE MEDICAL CENTER
DOB Cross Street(s):   EAST 30 STREET,    EAST 33 STREET
Status:   C - JOB IS SIGNED OFF 08/07/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/13/2016 8:48 AM
Application Entered:   12/13/2016 Job Start Date:   12/19/2016
Last Change:   08/07/2018 Job End Date:   05/31/2017
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     08/03/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $80.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYU LANGONE MEDICAL CTR
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   VP, FACILITIES


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008    16  70    22  45  20         
Buildings Total 16  70    22  45     20           
Total Units : 173 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 07/18/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M389991
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/14/2017 12/15/2017 BMP N (25) (0) Y
INSPECTION COMMENTS: PATIENTS IN PATIENT BEDROOMS. NO ACCESS.
 
(2) 04/06/2018 04/06/2018 AYC V (60) (5)
INSPECTION COMMENTS: FAIL. WAS NOT ABLE TO COMPLETE THE FULL INSPECTION. ONLY ABLE TO ACCESS THE BATHROOM IN THE PATIENT ROOM, ONE OFFICE AND THE 18TH FLOOR MECHANICAL ROOM.
 
(3) 07/18/2018 07/18/2018 AYC V X (55) (3)
INSPECTION COMMENTS: FAIL
 
(4) 07/18/2018 07/18/2018 AYC J Y (55) (0)
INSPECTION COMMENTS: FAIL
 
(5) 08/03/2018 08/03/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000012059
 
(6) 08/03/2018 08/03/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000012057
 
(7) 08/03/2018 08/03/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000012052

OBJECTION FOR APPLICATION #: M389991
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(FLOOR: 008) LAYIN LIGHT FIXTURES NOT SUPPORTED. ART. 410.36(B)
RSLV 04/06/2018 04/06/2018 07/18/2018
 
002 (999) OTHER
(FLOOR: 008)GAP BETWEEN WALLPAPERED FINISH SURFACE AND RECEPTACLES. ART. 312.3
RSLV 04/06/2018 04/06/2018 07/18/2018
 
003 (999) OTHER
(FLOOR: 008) BRANCH CIRCUITS NOT GROUPED IN THE PANEL. ART.
RSLV 04/06/2018 04/06/2018 07/18/2018
 
004 (999) OTHER
(FLOOR: 018)DISCONNECT SWITCHES NOT MARKED FOR HIGH VOLTAGE AND ARC FLASH. ARTS.110.3 & 110.16
RSLV 04/06/2018 04/06/2018 07/18/2018
 
005 (999) OTHER
(FLOOR: 018)BUSHINGS MISSING IN HIGH VOLTAGE DISCONNECT SWITCH. ART. 300.4(G
RSLV 04/06/2018 04/06/2018 07/18/2018
 
006 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 008)SJ CORD USED A PERMANENT WIRING METHOD IN THE WALL FOR CABINETLIGHTS. ART. 400.8
RSLV 07/18/2018 07/18/2018 08/03/2018
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008) OPEN KO. ART. 110.12(A)
RSLV 07/18/2018 07/18/2018 08/03/2018
 
008 (216) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
(FLOOR: 008)NO SEPARATION BETWEEN LINE AND LOW VOLTAGE WIRING IN CEILINGJUNCTION BOX. ART. 725.138
RSLV 07/18/2018 07/18/2018 08/03/2018