BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M389857
Premises: 250 WEST 24 STREET MANHATTAN BIN: 1084993     Block: 773   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 250 W 24TH ST Census Tract:   91 Health Area:  5200
BASEMENT SERVICE Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 06/22/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/08/2016 11:39 AM
Application Entered:   12/08/2016 Job Start Date:   12/08/2016
Last Change:   06/22/2017 Job End Date:   12/08/2017
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     06/16/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012580 Licensee Name: ANTHONY D LOMANTO
Firm: 004401 Firm Name: GENESIS ELECTRICAL GROUP
Firm Phone: 718-460-0263  Firm Address: 102-30 CORONA AVENUE CORP CORONA NY 11368 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $145.00
Other Work:   M216557
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: CHELSEA GARDENS OWNERS CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600 AMP 3 PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/05/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVING OBJECTIONS ISSUED TO APP # M216557 (GROUNDING)WORKDONE BY OTHER CONTRACTOR. ALSO REPLACEMENT OF 600 AMP SERVICE SWITCH

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M389857
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/02/2017 06/05/2017 CBK V (45) (4)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 06/16/2017 06/19/2017 STP C R (30) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M389857
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) NEUTRAL NOT BONDED TO ENCLOSURE IN 100A SERVICE SWITCH.
RSLV 06/02/2017 06/02/2017 06/16/2017
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) OPEN KO IN DISCONNECT SWITCH.
RSLV 06/02/2017 06/02/2017 06/16/2017
 
003 (999) OTHER
(BASEMENT) GEC RACEWAY NOT CONTINUOUS. 250.64
RSLV 06/02/2017 06/02/2017 06/16/2017
 
004 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
(GROUND FLOOR) NO SUPPLIMENTAL GROUND PROVIDED.
RSLV 06/02/2017 06/02/2017 06/16/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.