BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M389447
Premises: 343 EAST 63 STREET MANHATTAN BIN: 1044390     Block: 1438   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 340 E 64TH ST Census Tract:   110 Health Area:  4900
LOBBY/14TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/29/2016 10:44 AM
Application Entered:   11/29/2016 Job Start Date:   11/30/2016
Last Change:   08/22/2025 Job End Date:   11/29/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CARLOS CARDONA       On     01/22/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010890 Licensee Name: MICHAEL R OBERSTEIN
Firm: 004697 Firm Name: SOLEIRE ELECL SOLTNS CORP
Firm Phone: 347-617-3046  Firm Address: 450 LEXINGTON AVE, 4TH FLOOR NEW YORK NY 10017 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $242.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ST. TROPEZ CONDOMINIUM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  4 #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  (2) 100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB    63  37         
014    37  21                 
Buildings Total 100  58    10              
Total Units : 178 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/22/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALL OF LIGHTS & POWER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M389447
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/22/2019 01/22/2019 CDX V (55) (6)
INSPECTION COMMENTS: FAIL. CONTRACTOR TO NEXT INSPECTION. NEED SHOW LOCATION OF OCP ELECTRICAL PANEL MECHANICAL ROOM BASEMENT.

OBJECTION FOR APPLICATION #: M389447
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 014)FLOOR 14 COMMON AREA 314.20. 406.4 JUNTION BOXES SET BACK ,COMBUSTIBLE MATERIAL T-OUT
OPEN 01/22/2019 01/22/2019
 
002 (999) OTHER
(FLOOR: 014)FLOOR 14 110.3 MISSING COVER FOR MAIN SWICTH BOARD ENCLOSURE
OPEN 01/22/2019 01/22/2019
 
003 (999) OTHER
(BASEMENT)BSMT 400.14 NOT PROVIDED CORRECT FITTING FOR FLEXIBLE CORD (MECHANICAL ROOM LIGHTS)
OPEN 01/22/2019 01/22/2019
 
004 (999) OTHER
(BASEMENT)BSMT MECHANICAL ROOM PANEL 110.14(A) WRONG TERMINATION IN CB TWOWIRES
OPEN 01/22/2019 01/22/2019
 
005 (999) OTHER
(BASEMENT)BSMT MECHANICAL ROOM PANEL 210.4(B) NOT PROVIDED HANDLE TIES
OPEN 01/22/2019 01/22/2019
 
006 (999) OTHER
(LOBBY)LOBBY 314.20, 406.4 JUNCTION BOXES SET BACK . COMBUSTIBLE MATERIALLOBBY T-OUT
OPEN 01/22/2019 01/22/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.