Premises: 484 10 AVENUE MANHATTAN BIN: 1088764     Block: 735   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 455 W 37 ST Census Tract:   111
CELLAR ELECTRICAL ROOM Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
DOB Cross Street(s):   DYER AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 09/21/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/28/2016 Job Start Date:   11/17/2016
Last Change:   09/21/2018 Job End Date:   11/17/2019
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     09/18/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011590 Licensee Name: ALEKSANDR ROZOVSKY
Firm: 003113 Firm Name: ROZ-A-LITE ELEC'L CONTG I
Firm Phone: 718-369-5189  Firm Address: 159 20TH STREET..STE-401 BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $220.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53970     Submittal #: 16A0545  
Owner / Occup: FRANK VASTA
Owner Business Name: TF CORNERSTONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4#500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/28/2016 Notice: 1 - FIRST NOTICE 07/19/2018
Power Issued: 11/28/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PREVIOUSLY FILED APPLICATION M351865 DIDN'T HAVE ADVISORY BOARD INFORMATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M389377
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/20/2016 12/20/2016 MQY V (85) (2)
INSPECTION COMMENTS: ISSUED OBJECTIONS
 
(2) 07/19/2017 07/19/2017 GYM H X (50) (0) Y
INSPECTION COMMENTS: NEED DRAWING FOR THE NEXT INSPECTION. NO SHOW.
 
(3) 03/02/2018 03/02/2018 EDB V R (60) (2)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(4) 07/19/2018 07/19/2018 EDB V R (80) (1)
INSPECTION COMMENTS: JOB OK, ONLY ROOM LAYOUT NOT PER DRAWING. SEE ATTACHMENT AND DRAWING.
 
(5) 09/18/2018 09/18/2018 MJD C R (45) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M389377
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR)COPPER DETAIL IN TROUPH IS OF A SMALLER SIZE THAT SHOWS ON ADVISORYPLANS
RSLV 12/20/2016 12/20/2016 03/02/2018
 
002 (999) OTHER
(CELLAR) FUSES IN 400 AMP SWITCH IS NOT AS PER PLANS
RSLV 12/20/2016 12/20/2016 03/02/2018
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)RETAIL TROUGH FEED WITH 5 SET OF 500 KCM (FUSED FROM 3000 A ) ANDROOM LAYOUT AM. 110.2
RSLV 03/02/2018 03/02/2018 07/19/2018
 
004 (325) ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES
(CELLAR)SERVICE ELECTRIC ROOM USED FOR STORAGE AM.110.25
RSLV 03/02/2018 03/02/2018 07/19/2018
 
005 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) DRAWING NOT MACH ROOM LAYOUT AM. 110.2
RSLV 07/19/2018 07/19/2018 09/18/2018