Electrical Application Details for App #: M389250
Premises: 41 5 AVENUE MANHATTAN BIN: 1009252     Block: 568   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41 5TH AV Census Tract:   61 Health Area:  5700
APT3A Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 02/28/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/22/2016 8:50 AM
Application Entered:   11/22/2016 Job Start Date:   11/22/2016
Last Change:   02/28/2017 Job End Date:   11/22/2017
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     01/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011411 Licensee Name: HENRY KHODOSH
Firm: 003017 Firm Name: FALCO ELEC'L SERVICES INC
Firm Phone: 718-934-3600  Firm Address: 20 VESEY STREET SUITE 909 NEW YORK NY 10007 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $117.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHAR;ES CARSON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100AMP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3A  15  30    14  15         
Buildings Total 15  30    14  15              
Total Units : 77 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/22/2016 Notice: 1 - FIRST NOTICE 01/05/2017
Power Issued: 11/22/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M389250
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/05/2017 01/05/2017 PHG V (40) (4)
INSPECTION COMMENTS: NO SERVICE WORK DONE. COULD NOT READ NAME PLATE ON A/C DUE TO ACCESSIBILITY. PORCELAIN FIXTURE IN MASTER BED RM AT TIME OF INSPECTION
 
(2) 01/25/2017 01/26/2017 BUR C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M389250
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(FLOOR: 003) NO WORKING SPACE PROVIDED FOR A/C DISCONNECT 110.26
RSLV 01/05/2017 01/05/2017 01/25/2017
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 003) 150 FUSE FOR #2 WIRE RISER 240.3
RSLV 01/05/2017 01/05/2017 01/25/2017
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 003) LIGHT FIXTURE IN BABYS RM NO GROUND PROVIDED 250.122
RSLV 01/05/2017 01/05/2017 01/25/2017
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 003) AFCI PROTECTION NOT PROVIDED IN NEEDED AREAS 210.12
RSLV 01/05/2017 01/05/2017 01/25/2017