Electrical Application Details for App #: M388987
Premises: 340 PARK AVENUE MANHATTAN BIN: 1035473     Block: 1287   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 350 PARK AV Census Tract:   102 Health Area:  4800
10TH & 11TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   CITADEL
DOB Cross Street(s):   EAST 51 STREET,    EAST 52 STREET
Status:   C - JOB IS SIGNED OFF 05/01/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2016 4:09 PM
Application Entered:   11/15/2016 Job Start Date:   11/15/2016
Last Change:   05/01/2018 Job End Date:   02/24/2017
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     03/26/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011188 Licensee Name: GARY A FISHBONE
Firm: 001253 Firm Name: ROBERT B SAMUELS, INC
Firm Phone: 212-645-5150  Firm Address: 132 WEST 36TH STREET, 2ND FL NEW YORK NY 10018 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
009336 SAMUELS, DAVID I 001253 ROBERT B SAMUELS, INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,951.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: VORNADO REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  30  18-4#1;8GG;12-4#2
B. Over #2 to 1/0  2  1-3#4;#8G;1-3#3;#8G
C. Over 1/0 to 250 MCM  4  4-4#3/0;1#6G
D. Over 250 MCM  10  1-4#350;#4G
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  17  7-100A;6-200A;1-125A;175A
D. 3 Phase Over 225 AMPS  2  1-400A;1-300A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010    216  850  72  352  17  27  30  270 
011                      75 
Buildings Total 216  850  72  352     27     30     345 
Total Units : 1894 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  73227TP

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M388987
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/27/2017 07/28/2017 MQY V (220) (6)
INSPECTION COMMENTS: INPUTED BY MQY. ISSUED OBJECTIONS. DID NOT SEE GENERATOR OR GENERATOR FEEDER SPLICE BOX
 
(2) 03/26/2018 03/27/2018 MQY C R (60) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M388987
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 010) 500 KCMILL OVERFUSED AT 450 (315.16)
RSLV 07/27/2017 07/27/2017 03/26/2018
 
002 (999) OTHER
(FLOOR: 010)ATS-GEN-LPG DISCONNECT NEEDS NEUTRAL KIT AS PER MANUFACTURER 110.2
RSLV 07/27/2017 07/27/2017 03/26/2018
 
003 (999) OTHER
(FLOOR: 010) SIMULTANEOUS TRIP NEEDED ON MULTIWIRE BRANCH CKT 210.4
RSLV 07/27/2017 07/27/2017 03/26/2018
 
004 (999) OTHER
(FLOOR: 010)SECONDARY OF 75 KVA TRANSFORMER GOES FARTHER THAN 25 FT WITHOUTPROTECTION (240.21)
RSLV 07/27/2017 07/27/2017 03/26/2018
 
005 (999) OTHER
(ALL FLOORS)GEC INSIDE DERIVED CONDUCTORS RACEWAY OF TRANSFORMER NOT AS PER250.66
RSLV 07/27/2017 07/27/2017 03/26/2018
 
006 (999) OTHER
(ALL FLOORS)TRANSFORMERS NEED TO BE MARKED WITH PRIMARY AND SECONDARY
RSLV 07/27/2017 07/27/2017 03/26/2018