NYC Department of Buildings
Electrical Application Details for App #: M388969
Premises: 356 EAST 72 STREET MANHATTAN BIN: 1044862     Block: 1446   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 360 E 72ND ST Census Tract:   126 Health Area:  4200
APT C3500 Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 10/11/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2016 12:09 PM
Application Entered:   11/15/2016 Job Start Date:   11/15/2016
Last Change:   10/11/2017 Job End Date:   12/15/2016
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     10/11/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $229.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GREG COADY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2 SETS 1PHASE BX FOR 100A
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  2 100AMP 1PHASE PANELS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
035  C3500  30  31    14  30             
035  C3500  69  61  39  65             
Buildings Total 99  92  53  95                
Total Units : 348 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/26/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M388969
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/21/2017 03/21/2017 MLF N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR STATED THAT OFFICE WAS CALLED ON 3/20 AND CANCELLED APPOINTMENT
 
(2) 06/23/2017 06/26/2017 TUR V (60) (10)
INSPECTION COMMENTS: OBJECTIONS ISSUED , MADE CORRECTIONS ON APP FOR COUNTS (APT 3500 RIGHT SIDE AND LEFT SPLIT TO TWO APTS)
 
(3) 07/27/2017 07/28/2017 MQY J Y (44) (0)
INSPECTION COMMENTS: PANEL STILL IN CLOSET. INPUTED BY MQY
 
(4) 10/11/2017 10/11/2017 TUR C R (35) (0)
INSPECTION COMMENTS: CONTRACTORS REP STATES CLOSET IS UTILITY CLOSET, AND WILL ALWAYS BE UTILITY WITH NO COMBUSTIBLE MATERIALS

OBJECTION FOR APPLICATION #: M388969
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (218) UNAPPROVED FIXTURES INSTALLED IN ALL CLOTHES CLOSETS
(FLOOR: 035) 410.16(B) CLOSET LIGHT NOT APPROVED TYPE NOT ENCLOSED
RSLV 06/23/2017 06/23/2017 07/27/2017
 
002 (236) OUTSIDE A/C DISCONNECT NOT ACCESSIBLE
(FLOOR: 035) 440.14 WINDOW UNIT DOES NOT HAVE REQUIRED DISCONNECT
RSLV 06/23/2017 06/23/2017 07/27/2017
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 035) 408.4 DIRECTORY IN BOTH PANELS NOT ACCURATE OR COMPLETE
RSLV 06/23/2017 06/23/2017 07/27/2017
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 035) 210.8 PLUG MOLD NOT GFCI PROTECTED
RSLV 06/23/2017 06/23/2017 07/27/2017
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 035) 210.8 BATHROOM GFCI DEFECTIVE MISWIRED
RSLV 06/23/2017 06/23/2017 07/27/2017
 
006 (999) OTHER
(FLOOR: 035) 210.12 NOT ALL REQUIRED CIRCUITS AFCI PROTECTED
RSLV 06/23/2017 06/23/2017 07/27/2017
 
007 (999) OTHER
(FLOOR: 035)240.24D PANEL IN CLOSET ONE BOTH WERE RELOCATED FROM OLD POSITIONONE IN CLOSET ONE OUT OF CLOSET SEPARATE APTS
RSLV 06/23/2017 06/23/2017 10/11/2017
 
008 (999) OTHER
(FLOOR: 035)110.2 MATERIAL USED TO ENCLOSE OLD PANEL RISER SPLICE IS WOOD PANELNOT METAL
RSLV 06/23/2017 06/23/2017 07/27/2017
 
009 (999) OTHER
(FLOOR: 035)410.144 TRANSFORMER FOR KITCHEN UC LIGHTS OVER FRIDGE BOTH APTS (NOCOVER, NOT SECURED, NOT GROUNDED, AND WIRED THROUGH THE WALL WITH 2WIRE ZIP CORD NOT APPROVED)
RSLV 06/23/2017 06/23/2017 07/27/2017
 
010 (999) OTHER
(FLOOR: 035) 110.12 KO SEALS NOT INSTALLED IN OLD PANELS SPLICE BOX
RSLV 06/23/2017 06/23/2017 07/27/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.