| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
2 SETS 1PHASE BX FOR 100A |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
2 |
2 100AMP 1PHASE PANELS |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(218) |
UNAPPROVED FIXTURES INSTALLED IN ALL CLOTHES CLOSETS (FLOOR: 035) 410.16(B) CLOSET LIGHT NOT APPROVED TYPE NOT ENCLOSED |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 002 |
(236) |
OUTSIDE A/C DISCONNECT NOT ACCESSIBLE (FLOOR: 035) 440.14 WINDOW UNIT DOES NOT HAVE REQUIRED DISCONNECT |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 035) 408.4 DIRECTORY IN BOTH PANELS NOT ACCURATE OR COMPLETE |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 035) 210.8 PLUG MOLD NOT GFCI PROTECTED |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 035) 210.8 BATHROOM GFCI DEFECTIVE MISWIRED |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 006 |
(999) |
OTHER (FLOOR: 035) 210.12 NOT ALL REQUIRED CIRCUITS AFCI PROTECTED |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 007 |
(999) |
OTHER (FLOOR: 035)240.24D PANEL IN CLOSET ONE BOTH WERE RELOCATED FROM OLD POSITIONONE IN CLOSET ONE OUT OF CLOSET SEPARATE APTS |
RSLV |
06/23/2017 |
06/23/2017 |
10/11/2017 |
| |
| 008 |
(999) |
OTHER (FLOOR: 035)110.2 MATERIAL USED TO ENCLOSE OLD PANEL RISER SPLICE IS WOOD PANELNOT METAL |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 009 |
(999) |
OTHER (FLOOR: 035)410.144 TRANSFORMER FOR KITCHEN UC LIGHTS OVER FRIDGE BOTH APTS (NOCOVER, NOT SECURED, NOT GROUNDED, AND WIRED THROUGH THE WALL WITH 2WIRE ZIP CORD NOT APPROVED) |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |
| |
| 010 |
(999) |
OTHER (FLOOR: 035) 110.12 KO SEALS NOT INSTALLED IN OLD PANELS SPLICE BOX |
RSLV |
06/23/2017 |
06/23/2017 |
07/27/2017 |