| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1 200AMP MB 3PHASE POOL P |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS)240.3 POOL HEATER OVER CURRENT PROTECTION OVER SIZED MANUFACTURERSLISTS 225AMPS CURRENTLY ON 300AMP FUSE |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 002 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (ALL FLOORS) 590.3(D) TEMPORARY LIGHTING NOT REMOVED |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 003 |
(226) |
POOL LIGHT IS NOT PROPERLY GROUNDED (ALL FLOORS)680.6 POOL EQUIPMENT , LIGHTING , STRUCTURE, PANELS NOT GROUNDEDPROPERLY |
RSLV |
11/22/2016 |
11/22/2016 |
03/17/2017 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS)320.40 ARMORED CABLES NOT TERMINATED IN CEILING OF DECK BOX ROOM |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS)314.25 BOXES AND CONDELETS NOT COVERED THRU OUT POL MECHANICAL ROOM |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)680.22(A)(2) OUTLETS NOT SERVING POOL EQUIPMENT LESS THAN 10 FT FROMPOOL EDGE |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) 314.20 JUNCTION BOXES RECESSED MORE THAN 1/4" STONE |
RSLV |
11/22/2016 |
11/22/2016 |
12/28/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)314.4 GROUNDING IS NOT TERMINATED PROPERLY IN 15 DECK BOXES AND THERELATED SPLICE BOXES |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)AM 680.23 TRANSFORMERS SPECIFICATIONS FOR POOL LIGHT TRANSFORMERS |
RSLV |
11/22/2016 |
11/22/2016 |
03/17/2017 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)680.23 NEED SPEC FOR 15 LIGHT FIXTURE IN POOL AND HOT TUB NEED MOREINFO TO SEE INSTALLATION REQUIREMENT (IS IT A NICHE OR NO NICHEFIXTURE ETC) CANNOT REMOVE THIS OBJECTION WITHOUT SPECS |
RSLV |
11/22/2016 |
11/22/2016 |
03/17/2017 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)210.4 (B,D) GROUPING AND HANDLE TIES NEEDED IN POOL PANEL |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)110.16 ARCH FLASH LABELS NEEDED FOR POOL PANELS , AND DISCONNECTS ,POOL HEATER |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS)110.21,22 POOL PANELS , AND DISCONNECTS NEED IDENTIFICATION WITHDURABLE MEANS SEE ARTICLE FOR CONTENT |
RSLV |
11/22/2016 |
11/22/2016 |
12/28/2016 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)250.8(A) (1-8) GROUND BARS AND LUGS IN PANEL AND EQUIPMENT MOUNTEDWITH SELF TAP SCREWS |
RSLV |
11/22/2016 |
11/22/2016 |
12/12/2016 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS) 680.74 POOL BONDING NOT DONE PER CODE |
RSLV |
11/22/2016 |
11/22/2016 |
03/17/2017 |
| |
| 016 |
(999) |
OTHER (ALL FLOORS) 680.26 EQUIPOTNTIAL BONDING THRU OUT INSTALL |
RSLV |
11/22/2016 |
11/22/2016 |
03/17/2017 |
| |
| 017 |
(999) |
OTHER (ALL FLOORS) 680.41 HOT TUB EMERGENCY DISCONNECT |
RSLV |
11/22/2016 |
11/22/2016 |
12/28/2016 |
| |
| 018 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL (CELLAR)CONTRACTOR CHANGE FUSE IN 400 A S. SW.(POOL) TO 225 A IN EL RM OVER1000 KVA AM. 110.2 |
RSLV |
12/12/2016 |
12/12/2016 |
12/28/2016 |
| |
| 019 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) S. SW. FOR PULL NOT PROPERLY GND/BONDED 250 |
RSLV |
12/12/2016 |
12/12/2016 |
03/17/2017 |
| |
| 020 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) POOL: WET NICHE NOT PROPERLY GND 680.23 |
RSLV |
12/12/2016 |
12/12/2016 |
12/28/2016 |
| |
| 021 |
(999) |
OTHER (CELLAR) 680. THE BONDING OF THE NICHELESS FIXTURE NOT PER CODE ANDMANUFACTURERS SPECIFICATION PROVIDED THE INSTALL WAS MODIFIED DUE TOMETALLIC SHELL POOL DOES NOT HAVE INDIVIDUAL LUG FOR FIXTURE ANDTHERE IS A TOTAL OF 15 THE CONNECTION BETWEEN DECK BOX AND FIXTUREIS DONE WITH PVC AND BRASS CHANGE OVER MUST HAVE #8 GROUND TO |
RSLV |
12/28/2016 |
12/28/2016 |
03/17/2017 |
| |
| 022 |
(999) |
OTHER (CELLAR)680.23 TRANSFORMER NOT CONNECTED PER MANUFACTURES SPECIFICATION FORLIGHT SEE SERVICE SWITCH IN LINE AND CALLING FOR GFCI PROTECTION INBETWEEN FEED IN INSTRUCTIONS FOR LIGHT |
RSLV |
12/28/2016 |
12/28/2016 |
03/17/2017 |
| |
| 023 |
(999) |
OTHER (CELLAR) 680.26 BONDING GRID AROUND POOL AND ALL POINTS NEED TO BEPROPERLY INTERCONNECTED (NEED A RESISTANCE TEST PERFORMED FOR ALLPOINTS OF THE POOL AND RESULTS PROVIDED BY A CERTIFIED TESTINGCOMPANY ALSO WE NEEED THE ARCHITECTS DRAWINGS FOR THE POOL HOT TUBAND RELATED EQUIPMENT FOR NEXT INSPECTION |
RSLV |
12/28/2016 |
12/28/2016 |
03/17/2017 |