NYC Department of Buildings
Electrical Application Details for App #: M388072
Premises: 1192 PARK AVENUE MANHATTAN BIN: 1047125     Block: 1505   Lot: 40
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1192 PARK AV Census Tract:   160.01 Health Area:  2820
APT 12-A Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 06/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/21/2016 1:31 PM
Application Entered:   10/21/2016 Job Start Date:   10/24/2016
Last Change:   06/08/2018 Job End Date:   06/20/2017
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     10/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011286 Licensee Name: MICHAEL DISCENZA
Firm: 002688 Firm Name: SURE ELEC'L CONTR'G CORP.
Firm Phone: 718-227-2889  Firm Address: 360 TARGEE STREET STATEN ISLAND NY 10304 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $154.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GINO CAPOLINO
Owner Business Name: STRUCTURE-NY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  1 SET 3 # 3/0 WIRE1
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1 -40 CKT PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
012    18  28    12  18         
Buildings Total 18  28    12  18              
Total Units : 77 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/21/2016 Notice: 1 - FIRST NOTICE 10/11/2017
Power Issued: 10/21/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION OF EXISTING CIRCUITS/ NEW 150 AMP SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M388072
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/10/2017 10/11/2017 PHG V (45) (4)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR ALL WORK IN APT INCLUDING PANEL FEEDERS LIGHT COUNT OUTLET COUNT AC OUTLETS MOTOR KW ECT
 
(2) 10/26/2017 10/27/2017 DNM C R (22) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M388072
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 012) 4 WIRE ON 100 AMP BREAKER SUB PANEL 240.4
RSLV 10/10/2017 10/10/2017 10/26/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 012) LIVING ROOM LED DRIVER CORD CUT AND ALTERED 110.3
RSLV 10/10/2017 10/10/2017 10/26/2017
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 012) MASTER BATH ROOM 210.8
RSLV 10/10/2017 10/10/2017 10/26/2017
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 012) AFCI NEEDED T OUT 210.12
RSLV 10/10/2017 10/10/2017 10/26/2017