| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200A |
| C. 201 Up to 600 AMPS |
1 |
400A |
| D. 601 Up to 1200 AMPS |
2 |
800A, 1200A |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
37 |
#6 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
10 |
3/0 |
| D. Over 250 MCM |
5 |
500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
10 |
200A |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (ALL FLOORS) T-OUT |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 002 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (ALL FLOORS) FROM SPLIT AIR SYS TO CONDENSERS T-OUT |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)HANDLE TIES NOT PROVIDED , PANIC BAR NOT PROVIDED ELECTRICAL ROOMFIRE PUMP LETTERS NOT RIGHT SIZE , CONTRACTOR NEED FIX ISSUE WITHPLP METER AND 2 MDP PANELS WHICH RIGHT NOW SERVE AS ADDITIONALSERVICE SW (EXCEEDING LIMITS OF 6) |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)FIRE PUMP TO CONTROLLER NOT AS PER CODE (EQUIP.GR CONDUCTOR ) |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) T-OUT |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (ALL FLOORS) AT SERVICE SW T-OUT |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) NEED NEW APP FOR ONE EXTRA SERVICE SW INSTALLED |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) AFTER CORRECTION NEED T-OUT INSPECTION |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 009 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (CELLAR) IN FRONT PANEL UTILITY ROOM |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 010 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (CELLAR) PROPER IDENTIFICATION NOT PROVIDED |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 011 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (CELLAR) AT SERVICE SW T-OUT |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 012 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (ROOF) GENERATOR 4 WIRE SYSTEM |
RSLV |
03/09/2020 |
03/09/2020 |
04/17/2020 |
| |
| 013 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001) KITCHEN COUNTERTOP GFCI MISSING 210.8 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 014 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (ALL FLOORS) ARC FLASH LABELS REQUIRED 110.16 |
RSLV |
04/17/2020 |
04/17/2020 |
06/17/2020 |
| |
| 015 |
(139) |
VERTICAL CONDUCTOR SUPPORT IS NOT PER CODE (ALL FLOORS)2 SETS 500 MCM FEEDERS CONDUCTORS IN VERTICAL RACEWAYS SUPPORTMISSING 300. 19 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 016 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (BASEMENT) SERVICE SWITCHES NOT INDENTIFIED 230 70 110.21 |
RSLV |
04/17/2020 |
04/17/2020 |
06/17/2020 |
| |
| 017 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (BASEMENT)FIRE PUMP FEEDER TAP WITH IN 10 FT NOT OF PROPER SIZE 240.21 695.5 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 018 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (BASEMENT) 800 AMP SERVICE SWITCH NEUTRAL NOT BONDED 250.28 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 019 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (BASEMENT) GROUNDING RACEWAY BONDING JUMPER UNDER SIZE 250.66 |
RSLV |
04/17/2020 |
04/17/2020 |
06/09/2020 |
| |
| 020 |
(242) |
SERVICE ENTRANCE RACEWAY IS NOT SEALED (BASEMENT) SERVICE ENTRANCES CONDUITS NOT BONDED 250.92 |
RSLV |
04/17/2020 |
04/17/2020 |
06/09/2020 |
| |
| 021 |
(266) |
FIRE PUMP SERVICE SWITCH NOT PROPERLY IDENTIFIED (BASEMENT)FIRE PUMP SERVICE SW. SHALL BE MARKED "DO NOT DISC" LETTERS SHALL BEAT LEAST 1" 695.4 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 022 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (BASEMENT)SERVICE ENTRANCE BONDING BONDING JUMPERS UNDER SIZE 250.66 |
RSLV |
04/17/2020 |
04/17/2020 |
06/09/2020 |
| |
| 023 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (BASEMENT) THRU OUT |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 024 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) 60 AMP FIRE ALARM SERVICE NEUTRAL BAR NOT LISTED 110.2 |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 025 |
(127) |
NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM (ROOF)GENERATOR TESTING REPORT REQUIRED 700.4( NEED TO SUBMIT TO THEDEPARTMENT) |
RSLV |
04/17/2020 |
04/17/2020 |
06/17/2020 |
| |
| 026 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (ROOF) GENERATOR CONDUITS RACEWAY NOT CONTINUOUS 250.64 110.2 |
RSLV |
04/17/2020 |
04/17/2020 |
06/17/2020 |
| |
| 027 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (ROOF) ATS & BOILER ROOMS. |
RSLV |
04/17/2020 |
04/17/2020 |
05/18/2020 |
| |
| 028 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 012)ART. 314.28 PULL BOXES INSTALLED TO PROVIDE VERTICAL CONDUCTORSSUPPORT ON 12 FLOOR UNDERSIZED |
RSLV |
05/18/2020 |
05/18/2020 |
06/09/2020 |