Electrical Application Details for App #: M387845
Premises: 211 WEST 28 STREET MANHATTAN BIN: 1014260     Block: 778   Lot: 33
   

DOB NOW: Inspections


Filed: 211 W 28TH ST Census Tract:   95 Health Area:  5200
CELLAR-14TH FLR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
Related Job Number:    122143457
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   K - CLOSED/CANCELLED 06/17/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/17/2016 10:50 AM
Application Entered:   10/17/2016 Job Start Date:   10/17/2016
Last Change:   06/17/2020 Job End Date:   10/31/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     06/17/2020      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011877 Licensee Name: ANTHONY CERRITO
Firm: 003392 Firm Name: A & R ELEC'L MAINT. INC.
Firm Phone: 718-639-0800  Firm Address: 85-47 GRAND AVE ELMHURST NY 11373 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $2,829.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD SOSA
Owner Business Name: CHATEAU GC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  2  800A, 1200A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  37  #6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  10  3/0
D. Over 250 MCM  5  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  10  200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    30  24    30  78         
001    49  23  49             
002    18  32  18         
003    17  27  17             
004    17  27  17             
005    17  29  17             
006    17  29  17             
007    17  29  17             
008    17  29  17             
009    17  29  17             
010    17  29  17             
011    17  29  17             
012    17  29  17             
013    16  22  16             
014    16  22  16             
ROF    16  16    14         
Buildings Total 315  425  42  121  313     92           
Total Units : 1308 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 2 #10-Wire 2
Existing Meters 0 + New Meters 42 - Removed Meters 0 = Total Meters 42

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/17/2016 Notice: 1 - FIRST NOTICE 05/18/2020
Power Issued: 10/17/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387845
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/09/2020 03/10/2020 TOR V (135) (12)
INSPECTION COMMENTS: FAIL
 
(2) 04/17/2020 04/17/2020 GYM V R (240) (15)
INSPECTION COMMENTS: SEE APP # M00331464 INSPECTED ALL FLOORS.
 
(3) 05/18/2020 05/18/2020 MJD V Y (60) (1)
INSPECTION COMMENTS: FAIL, OBJECTION ISSUED, CONDITION CREATED WHILE CORRECTING EXISTING OBJECTION.
 
(4) 06/09/2020 06/09/2020 CDX J Y (60) (0)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. FOUR OBJECTION REMAIN.
 
(5) 06/17/2020 06/17/2020 TUR K R (1) (0)
INSPECTION COMMENTS: SEE REQ COMMENT

OBJECTION FOR APPLICATION #: M387845
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS) T-OUT
RSLV 03/09/2020 03/09/2020 04/17/2020
 
002 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(ALL FLOORS) FROM SPLIT AIR SYS TO CONDENSERS T-OUT
RSLV 03/09/2020 03/09/2020 04/17/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)HANDLE TIES NOT PROVIDED , PANIC BAR NOT PROVIDED ELECTRICAL ROOMFIRE PUMP LETTERS NOT RIGHT SIZE , CONTRACTOR NEED FIX ISSUE WITHPLP METER AND 2 MDP PANELS WHICH RIGHT NOW SERVE AS ADDITIONALSERVICE SW (EXCEEDING LIMITS OF 6)
RSLV 03/09/2020 03/09/2020 04/17/2020
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)FIRE PUMP TO CONTROLLER NOT AS PER CODE (EQUIP.GR CONDUCTOR )
RSLV 03/09/2020 03/09/2020 04/17/2020
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) T-OUT
RSLV 03/09/2020 03/09/2020 04/17/2020
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS) AT SERVICE SW T-OUT
RSLV 03/09/2020 03/09/2020 04/17/2020
 
007 (999) OTHER
(ALL FLOORS) NEED NEW APP FOR ONE EXTRA SERVICE SW INSTALLED
RSLV 03/09/2020 03/09/2020 04/17/2020
 
008 (999) OTHER
(ALL FLOORS) AFTER CORRECTION NEED T-OUT INSPECTION
RSLV 03/09/2020 03/09/2020 04/17/2020
 
009 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(CELLAR) IN FRONT PANEL UTILITY ROOM
RSLV 03/09/2020 03/09/2020 04/17/2020
 
010 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(CELLAR) PROPER IDENTIFICATION NOT PROVIDED
RSLV 03/09/2020 03/09/2020 04/17/2020
 
011 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(CELLAR) AT SERVICE SW T-OUT
RSLV 03/09/2020 03/09/2020 04/17/2020
 
012 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF) GENERATOR 4 WIRE SYSTEM
RSLV 03/09/2020 03/09/2020 04/17/2020
 
013 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) KITCHEN COUNTERTOP GFCI MISSING 210.8
RSLV 04/17/2020 04/17/2020 05/18/2020
 
014 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(ALL FLOORS) ARC FLASH LABELS REQUIRED 110.16
RSLV 04/17/2020 04/17/2020 06/17/2020
 
015 (139) VERTICAL CONDUCTOR SUPPORT IS NOT PER CODE
(ALL FLOORS)2 SETS 500 MCM FEEDERS CONDUCTORS IN VERTICAL RACEWAYS SUPPORTMISSING 300. 19
RSLV 04/17/2020 04/17/2020 05/18/2020
 
016 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT) SERVICE SWITCHES NOT INDENTIFIED 230 70 110.21
RSLV 04/17/2020 04/17/2020 06/17/2020
 
017 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(BASEMENT)FIRE PUMP FEEDER TAP WITH IN 10 FT NOT OF PROPER SIZE 240.21 695.5
RSLV 04/17/2020 04/17/2020 05/18/2020
 
018 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) 800 AMP SERVICE SWITCH NEUTRAL NOT BONDED 250.28
RSLV 04/17/2020 04/17/2020 05/18/2020
 
019 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(BASEMENT) GROUNDING RACEWAY BONDING JUMPER UNDER SIZE 250.66
RSLV 04/17/2020 04/17/2020 06/09/2020
 
020 (242) SERVICE ENTRANCE RACEWAY IS NOT SEALED
(BASEMENT) SERVICE ENTRANCES CONDUITS NOT BONDED 250.92
RSLV 04/17/2020 04/17/2020 06/09/2020
 
021 (266) FIRE PUMP SERVICE SWITCH NOT PROPERLY IDENTIFIED
(BASEMENT)FIRE PUMP SERVICE SW. SHALL BE MARKED "DO NOT DISC" LETTERS SHALL BEAT LEAST 1" 695.4
RSLV 04/17/2020 04/17/2020 05/18/2020
 
022 (277) BONDING JUMPER IS NOT PER ART 250.66
(BASEMENT)SERVICE ENTRANCE BONDING BONDING JUMPERS UNDER SIZE 250.66
RSLV 04/17/2020 04/17/2020 06/09/2020
 
023 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT) THRU OUT
RSLV 04/17/2020 04/17/2020 05/18/2020
 
024 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(BASEMENT) 60 AMP FIRE ALARM SERVICE NEUTRAL BAR NOT LISTED 110.2
RSLV 04/17/2020 04/17/2020 05/18/2020
 
025 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ROOF)GENERATOR TESTING REPORT REQUIRED 700.4( NEED TO SUBMIT TO THEDEPARTMENT)
RSLV 04/17/2020 04/17/2020 06/17/2020
 
026 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(ROOF) GENERATOR CONDUITS RACEWAY NOT CONTINUOUS 250.64 110.2
RSLV 04/17/2020 04/17/2020 06/17/2020
 
027 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(ROOF) ATS & BOILER ROOMS.
RSLV 04/17/2020 04/17/2020 05/18/2020
 
028 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 012)ART. 314.28 PULL BOXES INSTALLED TO PROVIDE VERTICAL CONDUCTORSSUPPORT ON 12 FLOOR UNDERSIZED
RSLV 05/18/2020 05/18/2020 06/09/2020