BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387672
Premises: 535 GREENWICH STREET MANHATTAN BIN: 1010366     Block: 597   Lot: 38
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 535 GREENWICH ST Census Tract:   37 Health Area:  6800
ENTIRE BUILDING Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
Related Job Number:    121185742
DOB Cross Street(s):   VANDAM STREET,    CHARLTON STREET
Status:   C - JOB IS SIGNED OFF 05/19/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/12/2016 1:05 PM
Application Entered:   10/12/2016 Job Start Date:   10/12/2016
Last Change:   05/19/2021 Job End Date:   06/10/2017
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     05/19/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 013007 Licensee Name: FINTAN J MURRAY
Firm: 003054 Firm Name: MIDLAND ELEC'L CO., INC.
Firm Phone: 718-894-4300  Firm Address: 37-31 58TH STREET WOODSIDE NY 11377 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011138 BEITLER, ALAN H 003054 MIDLAND ELEC'L CO., INC.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $944.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   GALLERY
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: URSULA DOBSON
Authorized Representative:  DENIS MC CARTHY
Relationship To Owner:   ELJIN CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1 X 600A SS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  5  1 X4#1/0, 4 X 4#1
C. Over 1/0 to 250 MCM  2  1 X 4#3/0, 1 X 4#4/0
D. Over 250 MCM  1  2 SETS 4 X 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  3 X 100A, 2 X 200A
D. 3 Phase Over 225 AMPS  1  1 X 400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    181  108    14  303  33     
Buildings Total 181  108    14  303     33         
Total Units : 646 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/12/2016 Notice: 1 - FIRST NOTICE 04/21/2021
Power Issued: 10/12/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387672
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/21/2021 04/21/2021 STP V (75) (9)
INSPECTION COMMENTS: FAIL. INSPECTED BASEMENT LEVEL ONLY, APP NOT FILED PROPERLY FOR ALL FLOORS AND ALL EQUIPMENT TOUT. DID NOT SEE WATER GROUND TERMINATION POINT OR SUPPLEMENT. INSPECTION INCOMPLETE.
 
(2) 04/23/2021 04/23/2021 PGR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-21-000013917
 
(3) 05/19/2021 05/19/2021 LV1 C R (60) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M387672
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (104) SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDING
(ALL FLOORS)230.43 SERVICE ENTRANCE FROM END BOX TO SERVICE SWITCH ENCLOSEDSHEETROCK TO BASEMENT SERVICE SWITCH
RSLV 04/21/2021 04/21/2021 05/19/2021
 
002 (999) OTHER
(ALL FLOORS) FILE FOR ALL FLOORS FOR ALL EQUIPMENT AS INSTALLED TOUT
RSLV 04/21/2021 04/21/2021 05/19/2021
 
003 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
(BASEMENT)422.10 WATER HEATER CONDUCTORS NOT SIZED FOR CONTINUOUS LOAD
RSLV 04/21/2021 04/21/2021 05/19/2021
 
004 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(BASEMENT) 240.21 TAP OFF 601A FUSE UNDERSIZED
RSLV 04/21/2021 04/21/2021 05/19/2021
 
005 (164) BOXES OR FITTINGS ARE MISSING
(BASEMENT)300.15 314.1 314.29 WATER HEATER ROOM LIGHT EXPOSED WIRES OUT SIDEOF FIXTURE INTO SHEETROCK
RSLV 04/21/2021 04/21/2021 05/19/2021
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) 110.16 ARC FLASH STICKERS NEEDED TOUT
RSLV 04/21/2021 04/21/2021 05/19/2021
 
007 (229) SPLICE BOXES NOT ACCESSIBLE
(BASEMENT)314.29 410.144 LED DRIVERS NO ACCESS INSIDE CEILING FOR BASEMENT LED
RSLV 04/21/2021 04/21/2021 05/19/2021
 
008 (255) NO FUSE COORDINATION EXISTS
(BASEMENT)240.12 601A OCPD FIRST LEVEL SERVICE SWITCH TO DOWNSTREAM DEVICES,SUBMIT FOR OFFICE REVIEW
RSLV 04/21/2021 04/21/2021 04/23/2021
 
009 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(BASEMENT) 110.3 110.14 DOUBLE LUGGING LOAD SIDE OF SERVICE SWITCH
RSLV 04/21/2021 04/21/2021 05/19/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order