| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
1 X 600A SS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
5 |
1 X4#1/0, 4 X 4#1 |
| C. Over 1/0 to 250 MCM |
2 |
1 X 4#3/0, 1 X 4#4/0 |
| D. Over 250 MCM |
1 |
2 SETS 4 X 350MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
3 X 100A, 2 X 200A |
| D. 3 Phase Over 225 AMPS |
1 |
1 X 400A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(104) |
SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDING (ALL FLOORS)230.43 SERVICE ENTRANCE FROM END BOX TO SERVICE SWITCH ENCLOSEDSHEETROCK TO BASEMENT SERVICE SWITCH |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) FILE FOR ALL FLOORS FOR ALL EQUIPMENT AS INSTALLED TOUT |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 003 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE (BASEMENT)422.10 WATER HEATER CONDUCTORS NOT SIZED FOR CONTINUOUS LOAD |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 004 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (BASEMENT) 240.21 TAP OFF 601A FUSE UNDERSIZED |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 005 |
(164) |
BOXES OR FITTINGS ARE MISSING (BASEMENT)300.15 314.1 314.29 WATER HEATER ROOM LIGHT EXPOSED WIRES OUT SIDEOF FIXTURE INTO SHEETROCK |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 006 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (BASEMENT) 110.16 ARC FLASH STICKERS NEEDED TOUT |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 007 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (BASEMENT)314.29 410.144 LED DRIVERS NO ACCESS INSIDE CEILING FOR BASEMENT LED |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |
| |
| 008 |
(255) |
NO FUSE COORDINATION EXISTS (BASEMENT)240.12 601A OCPD FIRST LEVEL SERVICE SWITCH TO DOWNSTREAM DEVICES,SUBMIT FOR OFFICE REVIEW |
RSLV |
04/21/2021 |
04/21/2021 |
04/23/2021 |
| |
| 009 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED (BASEMENT) 110.3 110.14 DOUBLE LUGGING LOAD SIDE OF SERVICE SWITCH |
RSLV |
04/21/2021 |
04/21/2021 |
05/19/2021 |