BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387624
Premises: 10 EAST 28 STREET MANHATTAN BIN: 1016894     Block: 857   Lot: 66
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 14 E 28TH ST Census Tract:   56 Health Area:  5700
ALL FLOORS SERVED, MR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10016 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/11/2016 6:31 PM
Application Entered:   10/11/2016 Job Start Date:   10/15/2016
Last Change:   08/22/2025 Job End Date:   10/15/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     01/31/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $872.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL GIORDANO
Owner Business Name: THE PRINCE GEORGE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  ELEVATORS
B. Each Additional 10 Floors Or Less  4  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/31/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  MODERNIZATION OF ELEVATOR DEVICE #'S 1P5136,37,38,40 BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION.(273018E) ELECTRICAL CONTROL AND LOAD SIDE WIRING BY ELEVATOR EMPLOYEES CONFORMING TO STANDARDS OF THE ELECTRICAL CODE ROT-161

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387624
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/31/2018 01/31/2018 EDB V (50) (2)
INSPECTION COMMENTS: DEV. # 1P5136, 1P5137. 1P5138 AND 1P5140 SEE ATTACHMENT.

OBJECTION FOR APPLICATION #: M387624
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) ELEV. RM. : NO OCP ON SECONDARY OF T-FMR 240.4
OPEN 01/31/2018 01/31/2018
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF)ELEV. RM. : NEW T-FMR(S) NOT PROPERLY GND 250.30
OPEN 01/31/2018 01/31/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order