BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387527
Premises: 303 HUDSON STREET MANHATTAN BIN: 1010362     Block: 597   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 315 HUDSON ST Census Tract:   37 Health Area:  6800
LOBBY Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    VANDAM STREET
Status:   C - JOB IS SIGNED OFF 05/14/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/10/2016 2:03 PM
Application Entered:   10/10/2016 Job Start Date:   10/14/2016
Last Change:   05/14/2018 Job End Date:   03/31/2017
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     03/27/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011377 Licensee Name: BENJAMIN BELOT
Firm: 003843 Firm Name: LEADER ELECTRIC CO., INC
Firm Phone: 212-665-0606  Firm Address: 857 SOUTHERN BLVD BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $284.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:   E - EMERGENCY LIGHTING LOCAL LAW 16/84 B - BOILER CONTROLS J-51 CERTIFICATION L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES SMITH
Owner Business Name: JRM CONSTRUCTION MGMT
Authorized Representative:  NEIL FAIREY
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB  LOB  190    16  32           
Buildings Total 190    16  32                
Total Units : 241 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/19/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387527
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/18/2017 04/18/2017 STP J (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR SHOWED, WILL RESCHEDULE STILL UNDER CONSTRUCTION.
 
(2) 03/16/2018 03/19/2018 HRB V (60) (2)
INSPECTION COMMENTS: FAILED FINAL
 
(3) 03/27/2018 03/27/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000004601
 
(4) 03/27/2018 03/27/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000004602

OBJECTION FOR APPLICATION #: M387527
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(FLOOR: 001) 2/0 WIRE FUSED AT 200 AMPS
RSLV 03/16/2018 03/16/2018 03/27/2018
 
002 (247) SIMULTANEOUS OPENING OF POLES
(FLOOR: 001) 12/3 CIRCUITS
RSLV 03/16/2018 03/16/2018 03/27/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back