BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387495
Premises: 306 BLEECKER STREET MANHATTAN BIN: 1010019     Block: 588   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 306 BLEECKER ST Census Tract:   73 Health Area:  6400
BASEMENT, 2ND, 3RD, & 4TH FLR. Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   BARROW STREET,    GROVE STREET
Status:   C - JOB IS SIGNED OFF 12/12/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/07/2016 4:33 PM
Application Entered:   10/07/2016 Job Start Date:   10/07/2016
Last Change:   12/12/2017 Job End Date:   10/07/2017
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     12/11/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012530 Licensee Name: HEMANCHAL DEONARINE
Firm: 004350 Firm Name: ELPO ELECTRICAL CONTG INC
Firm Phone: 718-384-6700  Firm Address: 50-03 METROPOLITAN AVE, SUITE B QUEENS NY 11385 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $393.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 3 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CALDWELL NANCY
Owner Business Name: COURDON BLEECKER LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  1OO AMPS EACH
B. 101 Up to 200 AMPS  1  200 A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  # 2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  100 AMPS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3P-200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  25  10             
003  10  20  15  10             
004  22  12             
Buildings Total 27  67  37  27                
Total Units : 163 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 1 #10-Wire 0
Existing Meters 5 + New Meters 5 - Removed Meters 5 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/07/2016 Notice: 1 - FIRST NOTICE 11/13/2017
Power Issued: 10/07/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SUPERSEDE PERMITS M339506, M342184,M343619 & WIRING FOR NEW4TH FLOOR APARTMENT. INSTALLATION OF NEW 3-PHASE, 200AMP SERVICE, NEW POWER RISERS TO THREE APARTMENTS. NEW BRANCH WIRING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387495
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/13/2017 11/13/2017 EDB V (50) (3)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 12/11/2017 12/12/2017 HRB C R (35) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M387495
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)RANGE HOOD/MIC. NOT ON INDIVIDUAL CIRCUIT AM. 422.16
RSLV 11/13/2017 11/13/2017 12/11/2017
 
002 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(CELLAR) 2ND TAP FOR APARTMENTS METER 240.21
RSLV 11/13/2017 11/13/2017 12/11/2017
 
003 (999) OTHER
(CELLAR)NO ARC FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 11/13/2017 11/13/2017 12/11/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.