BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387320
Premises: 95 CHAMBERS STREET MANHATTAN BIN: 1001629     Block: 149   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 95 CHAMBERS ST Census Tract:   21 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 07/10/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/04/2016 11:12 AM
Application Entered:   10/04/2016 Job Start Date:   10/04/2016
Last Change:   07/10/2017 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     07/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010593 Licensee Name: JOSE A MARENGO
Firm: 002839 Firm Name: ECS ELEC'L CONTG SERV INC
Firm Phone: 718-484-8884  Firm Address: 435 AUSTIN PLACE, SUITE E BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $217.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE DLUZYN
Owner Business Name: HUBB NYC PROPERTIES
Authorized Representative:  STEVE DLUZYN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A 3PHASE 4WIRE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4# 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP 42 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    70  45    20  70  16         
Buildings Total 70  45    20  70     16           
Total Units : 221 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 8 + New Meters 1 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/04/2016 Notice: 1 - FIRST NOTICE 04/07/2017
Power Issued: 10/04/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387320
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/06/2017 04/07/2017 EDB V (40) (4)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 07/07/2017 07/10/2017 CBK C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M387320
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(GROUND FLOOR) CONTRACTOR USE MC CABLE 517
RSLV 04/06/2017 04/06/2017 07/07/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) NO GFCI W/IN 6' FROM SINK 210.8
RSLV 04/06/2017 04/06/2017 07/07/2017
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) WATER FOUNTAIN 422.52
RSLV 04/06/2017 04/06/2017 07/07/2017
 
004 (999) OTHER
(GROUND FLOOR)NO ARC FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 04/06/2017 04/06/2017 07/07/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.