Electrical Application Details for App #: M387118
Premises: 148 BROADWAY MANHATTAN BIN: 1001087     Block: 64   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 150 BROADWAY Census Tract:   15.02 Health Area:  7700
8TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   JOB#4781
DOB Cross Street(s):   LIBERTY STREET,    CORTLANDT STREET
Status:   C - JOB IS SIGNED OFF 11/21/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2016 10:25 AM
Application Entered:   09/28/2016 Job Start Date:   09/28/2016
Last Change:   11/21/2017 Job End Date:   10/03/2016
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     11/20/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011831 Licensee Name: JAMES T GIORGIO, JR
Firm: 002393 Firm Name: B & G ELECL CONTR OF NY I
Firm Phone: 718-925-6900  Firm Address: 38-22 55 STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $340.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD LAVINO
Owner Business Name: JEMB REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1 SET 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  3  3-42CKT 400A PANELS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/11/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL (3) NEW PANELS IN THE 8TH FLOOR HALLWAY AND EXTEND CIRCUITS FROM THE OLD FUSE PANELS TO THE NEW BREAKER PANELS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387118
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/11/2017 05/11/2017 TOR V (30) (5)
INSPECTION COMMENTS: FAIL
 
(2) 11/20/2017 11/21/2017 CLC C R (33) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M387118
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(FLOOR: 008) MORE THAN 30 CONDUCTORS IN THE PIPE (ALL 3 PANELS 0
RSLV 05/11/2017 05/11/2017 11/20/2017
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 008) ALL BX IN ELECTRICAL ROOM
RSLV 05/11/2017 05/11/2017 11/20/2017
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 008) ALL J BOXES IN THE ELECTRICAL ROOM
RSLV 05/11/2017 05/11/2017 11/20/2017
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 008) ALL ELECTRICAL ROOM
RSLV 05/11/2017 05/11/2017 11/20/2017
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 008) ALL 3 PANELS
RSLV 05/11/2017 05/11/2017 11/20/2017