BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M387086
Premises: 67 LIBERTY STREET MANHATTAN BIN: 1001086     Block: 64   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 67 LIBERTY ST Census Tract:   15.02 Health Area:  7700
2ND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   LIBERTY PLACE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 12/27/2016 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/27/2016 5:15 PM
Application Entered:   09/27/2016 Job Start Date:   09/28/2016
Last Change:   12/27/2016 Job End Date:   10/08/2016
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     11/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010178 Licensee Name: ANTONIO TROIA
Firm: 004469 Firm Name: DAGNACHEW & ASSOCIATES IN
Firm Phone: 718-739-6776  Firm Address: 24-20 JACKSON AVENUE, STE#203 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $62.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL GORODNITSKY
Owner Business Name: COOLTECH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002      34  12  36  15         
Buildings Total   34  12  36     15           
Total Units : 99 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/04/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M387086
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/17/2016 10/18/2016 TOR V (40) (2)
INSPECTION COMMENTS: CONTRACTOR NOT FAMILIAR WITH A JOB
 
(2) 11/03/2016 11/04/2016 EDB V Y (40) (1)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 11/29/2016 11/29/2016 PHG C R (20) (0)
INSPECTION COMMENTS: BRANCH WIRING ONLY

OBJECTION FOR APPLICATION #: M387086
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 002) PANEL
RSLV 10/17/2016 10/17/2016 11/03/2016
 
002 (999) OTHER
(FLOOR: 002) NO HANDLE TIES PROVIDED T-OUT 210.4
RSLV 10/17/2016 10/17/2016 11/29/2016
 
003 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(FLOOR: 002)PANEL : OVER 10 CURRENT CONDUCTORS IN RACEWAY 310.15 B2A
RSLV 11/03/2016 11/03/2016 11/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back