BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M386804
Premises: 110 WEST 14 STREET MANHATTAN BIN: 1010642     Block: 609   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 110 W 14 ST Census Tract:   71 Health Area:  6100
FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 04/12/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/21/2016 3:24 AM
Application Entered:   09/21/2016 Job Start Date:   09/22/2016
Last Change:   04/12/2017 Job End Date:   10/01/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     04/10/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011972 Licensee Name: STEPHEN CHRISTOPHER
Firm: 003633 Firm Name: CHRISTOPHER ELECTRIC, INC
Firm Phone: 212-366-1443  Firm Address: 122 WEST 26TH STREET, STE1001 NEW YORK NY 10001 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $184.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOE SASSON
Owner Business Name: 110
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS SERVICE SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    34  10  34             
Buildings Total 34  10  34                
Total Units : 86 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/11/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WORK DONE BY OTHERS: M235077 AT OWNER M213096

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386804
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/11/2016 10/11/2016 STP V (30) (8)
INSPECTION COMMENTS: FAIL. DID NOT INSPECT AC EQUIPMENT AND NO ACCESS TO SPLICE BOX FOR XRAY MACHINE. X RAY MACHINE BLOCKING IT. CONTRACTOR DID NOT KNOW WHERE LED DRIVERS WHERE.
 
(2) 04/10/2017 04/12/2017 BMP C R (70) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. NEW OBJECTION REFERRED TO ENFORCEMENT. CERTIFIED.

OBJECTION FOR APPLICATION #: M386804
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) NO HANDLE TIES IN PANEL 210.4
RSLV 10/11/2016 10/11/2016 04/10/2017
 
002 (999) OTHER
(FLOOR: 001) X RAY SPLICE BOX TO SMALL 314.28
RSLV 10/11/2016 10/11/2016 04/10/2017
 
003 (999) OTHER
(FLOOR: 001) XRAY CB NOT FASTENED IN PLACE 408.36
RSLV 10/11/2016 10/11/2016 04/10/2017
 
004 (999) OTHER
(FLOOR: 001) XRAY DIS SW 4AWG OVERFUSED 240.4
RSLV 10/11/2016 10/11/2016 04/10/2017
 
005 (999) OTHER
(FLOOR: 001) NO HOSPITAL GRADE CABLE EXAM ROOMS 517.13
RSLV 10/11/2016 10/11/2016 04/10/2017
 
006 (999) OTHER
(FLOOR: 001) COVERS MISSING RECEPTACLES EXAM RM 314.25
RSLV 10/11/2016 10/11/2016 04/10/2017
 
007 (999) OTHER
(ALL FLOORS) NO ARC FLASH STICKERS 110.16
RSLV 10/11/2016 10/11/2016 04/10/2017
 
008 (999) OTHER
(BASEMENT) SEC EXTENDED OUT OF CON ED BOX AMND 230.46
RSLV 10/11/2016 10/11/2016 04/10/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back