Electrical Application Details for App #: M386680
Premises: 404 8 AVENUE MANHATTAN BIN: 1014333     Block: 780   Lot: 2
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 404 8TH AV Census Tract:   101 Health Area:  5200
APT 2 N Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):   WEST 30 STREET,    WEST 31 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/19/2016 12:02 PM
Application Entered:   09/19/2016 Job Start Date:   09/19/2016
Last Change:   08/22/2025 Job End Date:   12/31/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     12/01/2017      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 010904 Licensee Name: RYBURN A PHILLIPS
Firm: 002185 Firm Name: R.A. PHILLIPS ELEC'L CONT
Firm Phone: 718-493-1670  Firm Address: 131 KINGSTON AVENUE BROOKLYN NY 11213 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HASSAN ALBORATI
Owner Business Name: HASSAN ALBORATI 2NREALTY
Authorized Representative:  HASSAN ALBORATI
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  16 CKT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2N  12  20               
Buildings Total 12  20                  
Total Units : 40 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/17/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386680
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/16/2017 03/17/2017 MQY V (46) (6)
INSPECTION COMMENTS: ISSUED OBJECTIONS
 
(2) 12/01/2017 12/04/2017 EDB N (50) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR. NO SHOW.

OBJECTION FOR APPLICATION #: M386680
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002)ARC FAULT COMBINATION BREAKER NEEDED ON THE LIGHTING CKT (210.12)
OPEN 03/16/2017 03/16/2017
 
002 (999) OTHER
(FLOOR: 002) TAMPER RESISTANT RECEPTACLES NEEDED IN KITCHEN (406.11)
OPEN 03/16/2017 03/16/2017
 
003 (999) OTHER
(FLOOR: 002)SIMULTANEOUS TRIP NEEDED ON MULTIWIRE BRANCH CKTS (210.4)
OPEN 03/16/2017 03/16/2017
 
004 (999) OTHER
(FLOOR: 002)LIGHT FIXTURE OVER TUB NEEDS TO BE RATED FOR WET PURPOSES (410.10)
OPEN 03/16/2017 03/16/2017
 
005 (999) OTHER
(FLOOR: 002)STOVE RECEPTACLE, HOOD, AND KITCHEN LIGHTS ON THE SAME CKT (210.11210.52)
OPEN 03/16/2017 03/16/2017
 
006 (999) OTHER
(FLOOR: 002) RECEPTACLE NEEDED AT RIGHT SIDE OF SINK (210.52)
OPEN 03/16/2017 03/16/2017