BIS Menu  |  Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M386636
Premises: 244 EAST 60 STREET MANHATTAN BIN: 1043349     Block: 1414   Lot: 30
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 244 E 60TH ST Census Tract:   110 Health Area:  4900
ALL FLOORS SERVED, MR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   108
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/17/2016 11:44 AM
Application Entered:   09/17/2016 Job Start Date:   09/26/2016
Last Change:   08/22/2025 Job End Date:   09/26/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/18/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HOWARD PALEY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 10/19/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  MODERNIZATION OF ELEVATOR DEVICE # 1P25169 BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION(273018E). ELEVATOR CONTROL AND LOAD SIDE WIRING ONLY. LCD-87

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386636
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2017 10/05/2017 GYM N (30) (0) Y
INSPECTION COMMENTS: NO ACCESS. NO SHOW.
 
(2) 10/18/2017 10/19/2017 GYM V (60) (4)
INSPECTION COMMENTS: ELEVATOR.

OBJECTION FOR APPLICATION #: M386636
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) ELEVATOR MOTOR NOT GROUNDED 250.112
OPEN 10/18/2017 10/18/2017
 
002 (999) OTHER
(ROOF) 30 AMP DIS. SW. NEUTRAL BOND 250.24
OPEN 10/18/2017 10/18/2017
 
003 (999) OTHER
(ROOF) LB COVER MISSING 314.25
OPEN 10/18/2017 10/18/2017
 
004 (999) OTHER
(ROOF) ELEVATOR CONTROL PANEL GROUND NOT AS PER ART 250.8
OPEN 10/18/2017 10/18/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.