BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M386469
Premises: 303 HUDSON STREET MANHATTAN BIN: 1010362     Block: 597   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 315 HUDSON ST Census Tract:   37 Health Area:  6800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    VANDAM STREET
Status:   C - JOB IS SIGNED OFF 05/12/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/14/2016 10:08 AM
Application Entered:   09/14/2016 Job Start Date:   09/14/2016
Last Change:   05/12/2017 Job End Date:   01/03/2017
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     05/05/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011377 Licensee Name: BENJAMIN BELOT
Firm: 003843 Firm Name: LEADER ELECTRIC CO., INC
Firm Phone: 212-665-0606  Firm Address: 857 SOUTHERN BLVD BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $150.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:   E - EMERGENCY LIGHTING LOCAL LAW 16/84 L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEX SANTACROCE
Owner Business Name: CARRICKMORE P&D LLC
Authorized Representative:  NEIL FAIREY
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    54  44    18  54         
BAS  BAS  95    44  18  95  28  28         
Buildings Total 149  44  44  36  149     29           
Total Units : 451 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/18/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386469
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/18/2017 04/18/2017 BUR V (70) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 05/05/2017 05/05/2017 BMP C R (55) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M386469
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) BRANCH CIRCUITS IN 2 INCH NOT DERATED 310.15B2A
RSLV 04/18/2017 04/18/2017 05/05/2017
 
002 (999) OTHER
(CELLAR)TEMP WIRING STILL IN USE ,CONNECTED TO CEILING ROUND BOX 590.3
RSLV 04/18/2017 04/18/2017 05/05/2017
 
003 (999) OTHER
(CELLAR) A.C UNIT BREAKER NOT SIZED PROPERLY 110.3
RSLV 04/18/2017 04/18/2017 05/05/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.