BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M386437
Premises: 413 EAST 52 STREET MANHATTAN BIN: 1078257     Block: 1364   Lot: 5
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 415 E 52 ST Census Tract:   86.03 Health Area:  5000
APT. 8CA Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   A - ASSIGNED TO INSPECTOR JTE 02/11/2019 1:15 PM
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/13/2016 4:52 PM
Application Entered:   09/13/2016 Job Start Date:   09/14/2016
Last Change:   02/11/2019 Job End Date:   09/14/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   APPOINTMENT SCHEDULED - CONFIRMATION: 0211M
Last Inspection By:   MCPARTLAND, BRIAN       On     09/17/2018      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011693 Licensee Name: EVANGELINA APRILAKIS
Firm: 004165 Firm Name: EUROPA ELECTRIC OF NY COR
Firm Phone: 718-661-2660  Firm Address: 18-41 STEINWAY STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $63.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JANAN SHELTON
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  60 AMP 20 CTKS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008  8CA  12  12  12             
Buildings Total 12  12  12                
Total Units : 45 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 09/18/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386437
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/14/2016 10/17/2016 JRP J (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT READY FOR INSPECTION. JOB JUST STARTED
 
(2) 02/15/2018 02/15/2018 PHG V (30) (3)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR ALL WORK. CONTRACTOR WIRED ALL APT. FULL INSPECT NEEDED INSPECTED PANEL ONLY
 
(3) 09/04/2018 09/04/2018 BMP N (10) (0) Y
INSPECTION COMMENTS: OCCUPANT UNABLE TO SUPPORT THE INSPECTION. NO ACCESS.
 
(4) 09/17/2018 09/18/2018 BMP J X (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR ARRIVED LATE. HE SAID HE WOULD RESCHEDULE. JOB IN PROGRESS.
 
(5) ? (0) (1)
INSPECTION COMMENTS: No Inspection Comments For This Application

OBJECTION FOR APPLICATION #: M386437
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(FLOOR: 008)ALL PIPES FROM OLD PIPE SYSTEM IN NO BOND IN PANEL 300.10 250.8
OPEN 02/15/2018 02/15/2018
 
002 (999) OTHER
(FLOOR: 008) NO HANDLE TIES PROVIDED MULIT WIRE CKT 210.4
OPEN 02/15/2018 02/15/2018
 
003 (999) OTHER
(FLOOR: 008) NO BOLT ON BREAKER AFTER TAP 408.36
OPEN 02/15/2018 02/15/2018
 
004 (999) OTHER
(FLOOR: 008) APP DOES NOT MATCH INSTALL
OPEN



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back