Electrical Application Details for App #: M386386
Premises: 35 COOPER SQUARE MANHATTAN BIN: 1090311     Block: 461   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 200 E 6TH ST Census Tract:   38 Health Area:  6500
1ST FLOOR COMMERCIAL SPACE Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   COOPER SQUARE,    TARAS SHEVCHENKO PLACE
Status:   C - JOB IS SIGNED OFF 05/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/13/2016 6:20 AM
Application Entered:   09/13/2016 Job Start Date:   09/13/2016
Last Change:   05/03/2017 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     04/05/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012325 Licensee Name: DERRICK RAMDEEN
Firm: 004372 Firm Name: HIGH END NY ELECL CONTG C
Firm Phone: 718-738-3783  Firm Address: 132-10A LIBERTY AVENUE RICHMOND HILL NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $59.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   INTERNET COFFEE SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARUN BHATIA
Owner Business Name: COOPER & 6TH PROPERTY LLC
Authorized Representative:  JOHN BURKHARDT
Relationship To Owner:   GC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    50  25    12               
Buildings Total 50  25    12                  
Total Units : 87 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/17/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BRANCH WIRING FOR LIGHT & POWER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386386
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/16/2017 03/17/2017 EDB V (55) (4)
INSPECTION COMMENTS: A/C AND PANEL EXISTING.
 
(2) 04/05/2017 04/06/2017 BUR C R (50) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M386386
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
(GROUND FLOOR) CEILING OUTLET BOX MISSING COVER 314.25
RSLV 03/16/2017 03/16/2017 04/05/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) NO GFCI W/IN 6' FROM SINK 210.8
RSLV 03/16/2017 03/16/2017 04/05/2017
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(GROUND FLOOR) RECEPTACLE NOT FLUSH W/COMBUSTIBLE 314.20,21
RSLV 03/16/2017 03/16/2017 04/05/2017
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(GROUND FLOOR) EMT NOT SECURED T-OUT 358.30
RSLV 03/16/2017 03/16/2017 04/05/2017