| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
NEW PANEL |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (CELLAR) INSTALL GROUND AT SERVICE |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 002 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (CELLAR) DE-RATE BUNDLE OF BX CABLES IN SERVICE ROOM |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 003 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (CELLAR) SUPPORT CONDUITS IN BETWEEN PANELS |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 004 |
(999) |
OTHER (CELLAR)PROVIDE RISER DRAWING / LOAD LETTER WITH ALL LOADS FOR RESTAURANT |
RSLV |
03/28/2017 |
03/28/2017 |
06/05/2017 |
| |
| 005 |
(999) |
OTHER (CELLAR) KNOCKOUTS OPEN THROUGHOUT |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 006 |
(999) |
OTHER (CELLAR) SUPPORT LIGHTING IN KITCHEN , IN CORRECT CLIPS IN USE |
RSLV |
03/28/2017 |
03/28/2017 |
06/05/2017 |
| |
| 007 |
(999) |
OTHER (CELLAR) PROVIDE NETURAL BOND AT 200A SERVICE SWITCH |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 008 |
(999) |
OTHER (CELLAR) PROVIDE BOX EXTENDERS AT COMBUSTIBLE WALLS |
RSLV |
03/28/2017 |
03/28/2017 |
05/08/2017 |
| |
| 009 |
(999) |
OTHER (CELLAR) PROVIDE TYPEWRITTEN DIRECTORYS |
RSLV |
03/28/2017 |
03/28/2017 |
06/05/2017 |
| |
| 010 |
(999) |
OTHER (BASEMENT)WIRING METHODS SHALL NOT BE EXPOSED WITHIN THE COOKING HOOD 410.10 |
RSLV |
05/08/2017 |
05/08/2017 |
06/05/2017 |
| |
| 011 |
(999) |
OTHER (BASEMENT) COMMERCIAL KITCHEN GFCI REQUIRED ALL RECEPTACLES 210.8 |
RSLV |
05/08/2017 |
05/08/2017 |
06/05/2017 |
| |
| 012 |
(999) |
OTHER (ROOF) LFMC OVER 6FL 350.12 |
RSLV |
05/08/2017 |
05/08/2017 |
06/05/2017 |