Electrical Application Details for App #: M386244
Premises: 207 WEST 25 STREET MANHATTAN BIN: 1014211     Block: 775   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 207 W 25TH ST Census Tract:   91 Health Area:  5200
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/08/2016 1:56 PM
Application Entered:   09/08/2016 Job Start Date:   09/09/2016
Last Change:   08/22/2025 Job End Date:   09/08/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     06/20/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011360 Licensee Name: SERVULUS BILLY
Firm: 003868 Firm Name: POWERONE ELECT'L CONTRG
Firm Phone: 718-241-3236  Firm Address: 1459 BASSETT AVENUE INC BRONX NY 10461 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $220.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HAYK HAJINLIAN
Owner Business Name: KAPRIELIAN ENTERPRISES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1 400AMP FUSED
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1 SET OF 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/08/2016 Notice: 1 - FIRST NOTICE 06/21/2017
Power Issued: 09/08/2016 Response:  

Follow-Up:
Contractor's Comments:  INSTALLING NEW METER FOR 10TH FLOOR.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M386244
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2017 06/08/2017 TUR N (45) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW NO ACCESS TO WORK
 
(2) 06/20/2017 06/21/2017 CBK V (45) (2)
INSPECTION COMMENTS: SEE OBJECTION DETAILS. TWO SETS OF 3/0 OBSERVED.

OBJECTION FOR APPLICATION #: M386244
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)SERVICE IN EXCESS OF 1000KVA, CONTRACTOR INSTALL 400AMP FUSE ONSECOND LEVEL.
OPEN 06/20/2017 06/20/2017
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) CONDUITS NOT PROPERLY SUPPORTED.
OPEN 06/20/2017 06/20/2017