BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M385930
Premises: 130 EAST 69 STREET MANHATTAN BIN: 1042479     Block: 1403   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 150 E 69 ST Census Tract:   120 Health Area:  4100
AP 8 DE Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 01/03/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/30/2016 2:02 PM
Application Entered:   08/30/2016 Job Start Date:   08/31/2016
Last Change:   01/03/2018 Job End Date:   10/15/2016
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     12/27/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009165 Licensee Name: CARMINE J CAMENZULI
Firm: 003589 Firm Name: JLC ELEC'L CONTR'G INC
Firm Phone: 718-932-2499  Firm Address: 14-45 BROADWAY LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $212.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIAN GOLDMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  2  1PHASE FROM OLD PANEL
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  1PHASE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ8  8 DE  88  60  55               
MZ8  8DE  88  60  55  88             
Buildings Total 176  120  12  110  88                
Total Units : 506 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/15/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M385930
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/15/2017 11/15/2017 TUR V (65) (4)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 12/27/2017 12/27/2017 CLC C R (120) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M385930
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (236) OUTSIDE A/C DISCONNECT NOT ACCESSIBLE
(FLOOR: 008) 440.14 ALL PTAC NO ACCESSIBLE DISCONNECTS
RSLV 11/15/2017 11/15/2017 12/27/2017
 
002 (999) OTHER
(FLOOR: 008)210.12 NOT ALL EREQUIRED CIRCUITS ARE ARCH FAULT PROTECTD BOTHPANELS
RSLV 11/15/2017 11/15/2017 12/27/2017
 
003 (999) OTHER
(FLOOR: 008)110.2 QUAD BREAKERS DEFCTIVE NOT INSTALLED AS PER MANUFACTURERRESTRICTIONS REMOVED
RSLV 11/15/2017 11/15/2017 12/27/2017
 
004 (999) OTHER
(FLOOR: 008)110.2 OLD PANE, INERTS NOT REMOVED WITH SPLICES AND MUST BE SECURED
RSLV 11/15/2017 11/15/2017 12/27/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back