| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
4X(4)#6,1X(4)#3 |
| B. Over #2 to 1/0 |
3 |
3X(4)1/0 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
8 |
5X3P-200A, 3X3P-60A, |
| D. 3 Phase Over 225 AMPS |
1 |
1-250A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 005) NO ILLUMINATION IN EL. CLOSET 110.26 |
RSLV |
09/02/2016 |
09/02/2016 |
10/06/2016 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) BATHROOM LIGHT MISSING COVER |
RSLV |
09/02/2016 |
09/02/2016 |
10/06/2016 |
| |
| 003 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (CELLAR) TEMP. WIRING IN USE (EL. SERV. RM.) |
RSLV |
09/02/2016 |
09/02/2016 |
10/06/2016 |
| |
| 004 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL (CELLAR)CONTRACTOR INSTALLED 3 X 1200 A S. SW(S) AND 1 X 60 A S. SW. |
RSLV |
09/02/2016 |
09/02/2016 |
12/23/2016 |
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED (OPEN SPACE) OUTDOOR RECEPTACLE MISSING COVER |
RSLV |
09/02/2016 |
09/02/2016 |
10/06/2016 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (OPEN SPACE) OUTDOOR RECEPTACLE NOT WEATHER-RESISTANT TYPE 406.8 |
RSLV |
09/02/2016 |
09/02/2016 |
10/06/2016 |
| |
| 007 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ROOF) GENERATOR MISSING WORKING PLATFORM |
RSLV |
09/02/2016 |
09/02/2016 |
12/23/2016 |