BIS Menu  |  Elevators  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M385611
Premises: 529 BROADWAY MANHATTAN BIN: 1007583     Block: 498   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 529 BROADWAY Census Tract:   49 Health Area:  6800
ALL BUILDING Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Related Job Number:    121235608
DOB Cross Street(s):   SPRING STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 01/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/22/2016 11:18 AM
Application Entered:   08/22/2016 Job Start Date:   08/22/2016
Last Change:   01/14/2017 Job End Date:   08/22/2017
Appointment Status:   
Last Inspection By:   URIM SYLA       On     12/23/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012079 Licensee Name: DARIUSZ GRYGLEWSKI
Firm: 004264 Firm Name: FSM ELECTRICAL CORPORATIO
Firm Phone: 718-482-9151  Firm Address: 11-20 37TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $909.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121235608
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KENNETH HART
Owner Business Name: HARCO CONSULTING
Authorized Representative:  TINA ACOSTA
Relationship To Owner:   PM


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  4X(4)#6,1X(4)#3
B. Over #2 to 1/0  3  3X(4)1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  5X3P-200A, 3X3P-60A,
D. 3 Phase Over 225 AMPS  1  1-250A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    23  16  25  17  27     
001             
002           
003             
004           
005      10         
006       
ROF        29  626         
Buildings Total 22  61  44  22  75     646     57      
Total Units : 927 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/22/2016 Notice: 1 - FIRST NOTICE 09/06/2016
Power Issued: 08/22/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACEMENT OF M373674. ELEVATORS POWER PROVIDED AND LEFT IN DISCONNECT SWITCH. OUR SCOPE OF WORK INVOLVES WITH VANILLABOX BASE CONTRACT OF THE BUILDING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M385611
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/02/2016 09/06/2016 EDB V (185) (7)
INSPECTION COMMENTS: CONTRACTOR NEED TO RE FILE APPLICATION. AP. # M384630 SIGNED OFF , HAVE ONLY 1 X 1200 A S. SW. ( # 53891 ).
 
(2) 10/06/2016 10/07/2016 PHG J Y (45) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED CONTRACTOR NEEDS TO FILE FOR OTHER SERVICE SW UNDER ADVISORY BOARD
 
(3) 12/07/2016 12/08/2016 UMS N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW, NO ANSWER
 
(4) 12/23/2016 12/27/2016 UMS C R (30) (0)
INSPECTION COMMENTS: SEE ADVISORY BOARD APPLICATIONS M384630, M388628

OBJECTION FOR APPLICATION #: M385611
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 005) NO ILLUMINATION IN EL. CLOSET 110.26
RSLV 09/02/2016 09/02/2016 10/06/2016
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(ALL FLOORS) BATHROOM LIGHT MISSING COVER
RSLV 09/02/2016 09/02/2016 10/06/2016
 
003 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(CELLAR) TEMP. WIRING IN USE (EL. SERV. RM.)
RSLV 09/02/2016 09/02/2016 10/06/2016
 
004 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR)CONTRACTOR INSTALLED 3 X 1200 A S. SW(S) AND 1 X 60 A S. SW.
RSLV 09/02/2016 09/02/2016 12/23/2016
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
(OPEN SPACE) OUTDOOR RECEPTACLE MISSING COVER
RSLV 09/02/2016 09/02/2016 10/06/2016
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(OPEN SPACE) OUTDOOR RECEPTACLE NOT WEATHER-RESISTANT TYPE 406.8
RSLV 09/02/2016 09/02/2016 10/06/2016
 
007 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(ROOF) GENERATOR MISSING WORKING PLATFORM
RSLV 09/02/2016 09/02/2016 12/23/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.