Electrical Application Details for App #: M385389
Premises: 221 WEST 23 STREET MANHATTAN BIN: 1014148     Block: 773   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 225 W 23RD ST Census Tract:   91 Health Area:  5200
APT 5G Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   APT 5G
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 02/16/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/16/2016 11:14 AM
Application Entered:   08/16/2016 Job Start Date:   08/16/2016
Last Change:   02/16/2018 Job End Date:   10/01/2016
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     02/15/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012374 Licensee Name: SHEFKI ARIFI
Firm: 002528 Firm Name: KLEAR ELECTRICAL CORP.
Firm Phone: 718-361-5366  Firm Address: 31-00 47TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (7  Stores, 127 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 23STREET OWNER LLC
Authorized Representative:  JACKIE RENTON
Relationship To Owner:   ASSET MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  5G                 
Buildings Total                   
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/15/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MINOR RENOVATION OF EXISTING SPACE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M385389
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2016 11/01/2016 BUR J (45) (0) Y
INSPECTION COMMENTS: JOB NOT READY FOR INSPECTION
 
(2) 11/21/2016 11/22/2016 EDB V (30) (4)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 12/12/2016 12/15/2016 PHG V X (30) (4)
INSPECTION COMMENTS: COULD NOT LOCATE PANEL FEED. BATH RM AND KITCHEN GFCI NO POWER AT TIME OF INSPECTION. INSPECTION NOT FINAL
 
(4) 01/10/2017 01/11/2017 MLF J Y (25) (0)
INSPECTION COMMENTS: OBJECTIONS STILL EXIST
 
(5) 02/15/2018 02/16/2018 CJH C R (35) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: M385389
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 005) PANEL : NEUTRAL BONDED 250.24
RSLV 11/21/2016 11/21/2016 01/10/2017
 
002 (340) RECEPTACLES NOT TAMPERPROOF
(FLOOR: 005) RECEPTACLE NOT TAMPERPROOF 406.11
RSLV 11/21/2016 11/21/2016 01/10/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 005) NEW LINE: NO AFCI 210.8
RSLV 11/21/2016 11/21/2016 01/10/2017
 
004 (999) OTHER
(FLOOR: 005)PANEL : MULTIWIRE CKT. NO GROUPED NO SIMULT. DISC. 210.4
RSLV 11/21/2016 11/21/2016 01/10/2017
 
005 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 005) BOXES NOT BONDED T OUT 250.148
RSLV 12/12/2016 12/12/2016 02/15/2018
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 005) UNDER SIZE GROUND FOR RECEPTACLES T OUT 250.122
RSLV 12/12/2016 12/12/2016 02/15/2018
 
007 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 005) DIRECTORY INCOMPLETE
RSLV 12/12/2016 12/12/2016 01/10/2017
 
008 (999) OTHER
(FLOOR: 005) LIGHT IN SHOWER NOT LISTED FOR DAMP LOCATION 410.10
RSLV 12/12/2016 12/12/2016 02/15/2018