| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
97 |
77-#2 4-#3 16-#4 |
| B. Over #2 to 1/0 |
31 |
31-#1/0 |
| C. Over 1/0 to 250 MCM |
38 |
4-#4/0 31-#3/0 3-#2/0 |
| D. Over 250 MCM |
65 |
12-#600 26-#500 6-#400 .. |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
124 |
112-125A 12-200A |
| C. 3 Phase Up to 225 AMPS |
37 |
5-60A 16-100A 2-150A ... |
| D. 3 Phase Over 225 AMPS |
13 |
4-#400A 4-600A 4-800A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 022) KITCHEN ISLAND SOUTH TOWER |
RSLV |
06/17/2019 |
06/17/2019 |
10/03/2019 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 022) AFCI DEFECTIVE SOUTH TOWER |
RSLV |
06/17/2019 |
06/17/2019 |
10/03/2019 |
| |
| 003 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) FLOORS 23,24,25 SOUTH TOWER |
RSLV |
06/17/2019 |
06/17/2019 |
10/03/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)ALL KITCHENS WITH SINK TO ONE SIDE OF COUNTER TOP NEED 2 CIRCUITS210.52 |
RSLV |
06/17/2019 |
06/17/2019 |
10/03/2019 |
| |
| 005 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (ALL FLOORS) T-OUT |
RSLV |
09/06/2019 |
09/06/2019 |
10/03/2019 |
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) EXIT SIGNS NOT PROPERLY SUPPORTED T-OUT |
RSLV |
09/06/2019 |
09/06/2019 |
10/03/2019 |
| |
| 007 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (ALL FLOORS) T-OUT |
RSLV |
09/06/2019 |
09/06/2019 |
10/03/2019 |
| |
| 008 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS) T-OUT |
RSLV |
09/06/2019 |
09/06/2019 |
10/03/2019 |